Hello
I have just started a new loft conversion and would like to install 4 extra double sockets would it be best to run a fused spur off a second floor socket or extend the ring to the loft space.  Any advice would be greatly appreciated thanks.


Title: Re: Loft Conversion
Post by supersparky on May 14th, 2004, 2:32pm

best to extend the ring.
if you have the option stick a new circuit in on a 20amp breaker to supply the loft- makes identification and isolation much easyer- also means that you wont increase the load on the ring  ;D

ss

Title: Re: Loft Conversion
Post by securespark on May 18th, 2004, 1:23am

Although if you have a sep ring upstairs, there isn't usually a great load on first floor ring, not like ground.