DIY Forum >> Electrical Questions >> PIR light into socket https://www.askthetrades.co.uk/cgi-bin/yabb/YaBB.pl?num=1448889514 Message started by yid on Nov 30th, 2015, 1:18pm |
Title: PIR light into socket Post by yid on Nov 30th, 2015, 1:18pm I have had outside sockets which are wired to my comsumer unit with trips and I want to install outside pir light into socket. if I wire it with 2.5m cable and put 13amp socket on the end, would that be legal and safe? |
Title: Re: PIR light into socket Post by fife spark on Dec 19th, 2015, 5:36pm You can't use twin and earth in a plug. you could use 1mm or 1.5mm flex. the fuse would need to be 3A. The flex would need to be suitable for use outside and correctly run. The circuit will need to be protected by a RCD. Is it a IP rated socket? |