Joining 10mm cooker cable (Read 26918 times)
TonyB
Newbie
*
Offline


Posts: 4


Total Thanks: 0
For This Post: 0


Gender: male

Joining 10mm cooker cable
May 27th, 2004, 8:56pm
 
???

I am about to revamp a kitchen which will mean moving the cooker control unit (the new control unit will not have a 13 Amp socket on it). Is it possible and legal to join 10mm cable and if so how ?

Many thanks for any advice.

TonyB
Back to top
 
Thank User For This Post  
IP Logged
 
supersparky
Administrator
Trade Member
Author
*****
Offline


Posts: 6097


Total Thanks: 3
For This Post: 0


Gender: male

Trade: Electrician



Re: Joining 10mm cooker cable
Reply #1 - May 27th, 2004, 9:10pm
 
it is legal
you will have to use un insulated crimps to do it with and heat sleeveing, unless the joint will be acsessable, in which case you may use a 45amp/50amp junctionbox
if it is going to be jointed in the wall this probrably wont be convenient(the uninsulated splices require a special tool to do!) the best way would be to pull the cable up into the floor above and join it there, with one new piece- it saves having a joint in the wall.

what ever you do make sure its done well, make sure there is no un insulated copper visable (the earth MUST be sheathed with earth sleveing) and make sure all the screws are tight, and the wires firmly in place.

ss
Back to top
 
Thank User For This Post WWW  
IP Logged
 
Lectrician
Administrator
Trade Member
Author
*****
Offline

Ask The Trades
Posts: 8814


Total Thanks: 108
For This Post: 0


Braunton, North Devon, United Kingdom
Braunton, North Devon
United Kingdom

Gender: male

Trade: Electrician



Re: Joining 10mm cooker cable
Reply #2 - May 27th, 2004, 9:19pm
 
Joining 10mm - god.

This size cable doesn't fit standard joint boxes, best to use something like a Gewiss 'plastic' box, with either moulded terminal blocks or din rail terminals inside.  Use large TRS glands for the cable in and out of this box.

Im sure Supersparky will agree Smiley
Back to top
 

Need to post a picture? Click HERE for info!
Thank User For This Post WWW View members image gallery  
IP Logged
 
TonyB
Newbie
*
Offline


Posts: 4


Total Thanks: 0
For This Post: 0


Gender: male

Re: Joining 10mm cooker cable
Reply #3 - May 27th, 2004, 10:15pm
 

Thanks for the 2 suggestions, putting the join in the ceiling void would have been the easiest but it is not an option (ceiling is 6" thick concrete).

Can I use this plastic box and put it in the space left by the old control unit, plaster over the box and tile the wall?

Rgds,

TonyB
Back to top
 
Thank User For This Post  
IP Logged
 
rabbit_rabbit
Re: Joining 10mm cooker cable
Reply #4 - May 27th, 2004, 10:31pm
 
Crimp and put crimp joints into a 'ChocBox' (about 90p to £1.00). Lock the Chocbox with supplied screw. Then TEST to make sure all is OK and THEN shove into hole and plaster it up.

RR
Back to top
 
Thank User For This Post  
IP Logged
 
supersparky
Administrator
Trade Member
Author
*****
Offline


Posts: 6097


Total Thanks: 3
For This Post: 0


Gender: male

Trade: Electrician



Re: Joining 10mm cooker cable
Reply #5 - May 27th, 2004, 10:32pm
 
no unfortunatly, joints must be acsessable, is there no way you could hide it higher up the wall?
is the cable in singles(in conduit) or is it twin and earth(the 2 cores in a sheath with earth)

looks like your going towards a splice joint

other option is putting a blank plate over old hole and  joining inside there- however, This MUST not get plastered over Sad

ss
Back to top
 
Thank User For This Post WWW  
IP Logged
 
rabbit_rabbit
Re: Joining 10mm cooker cable
Reply #6 - May 27th, 2004, 10:37pm
 
(Revert) timing SS? A Crimp is not a JB and is not subject to inspection (that's a question SS)?

RR

Back to top
 
Thank User For This Post  
IP Logged
 
LSpark
Global Moderator
Trade Member
Author
*****
Offline


Posts: 8069


Total Thanks: 3
For This Post: 0


London, UK, United Kingdom
London, UK
United Kingdom

Gender: male

Trade: Electrician



Re: Joining 10mm cooker cable
Reply #7 - May 27th, 2004, 10:49pm
 
i agree, it's a good one too
Back to top
 
Thank User For This Post View members image gallery  
IP Logged
 
supersparky
Administrator
Trade Member
Author
*****
Offline


Posts: 6097


Total Thanks: 3
For This Post: 0


Gender: male

Trade: Electrician



Re: Joining 10mm cooker cable
Reply #8 - May 27th, 2004, 10:52pm
 
timing! rabbit, posted at the same time as you
wasnt replying To you lol  Wink
Grin
nece to see we agree though

and ls, eh?
ss
Back to top
« Last Edit: May 27th, 2004, 10:53pm by supersparky »  
Thank User For This Post WWW  
IP Logged
 
LSpark
Global Moderator
Trade Member
Author
*****
Offline


Posts: 8069


Total Thanks: 3
For This Post: 0


London, UK, United Kingdom
London, UK
United Kingdom

Gender: male

Trade: Electrician



Re: Joining 10mm cooker cable
Reply #9 - May 27th, 2004, 11:09pm
 
nvm, il find out lol
Back to top
 
Thank User For This Post View members image gallery  
IP Logged
 
TonyB
Newbie
*
Offline


Posts: 4


Total Thanks: 0
For This Post: 0


Gender: male

Re: Joining 10mm cooker cable
Reply #10 - May 28th, 2004, 8:51pm
 

You guys certainly have different views! Not sure where we are with this but in answer to the cable type, it is a single 2 core + Earth.

What is involved with this splicing?

Rgds,

TonyB
Back to top
 
Thank User For This Post  
IP Logged
 
scotspark
Trade Member
*****
Offline

mmmmm it's gonna cost
you!!
Posts: 3074


Total Thanks: 10
For This Post: 0


scotland, Scotland
scotland
Scotland

Gender: male

Trade: Electrician



Re: Joining 10mm cooker cable
Reply #11 - May 28th, 2004, 9:00pm
 


hope this helps tony

doubt you will have crimps or a crimper so best to join it in the original box with terminal block and put a blank plater over it 8)
Back to top
 

brown to red and blue to f****&&&&ommited!!!!!!!!!!!!!!!!!!!!!!!!!!!
Thank User For This Post View members image gallery  
IP Logged
 
rabbit_rabbit
Re: Joining 10mm cooker cable
Reply #12 - May 28th, 2004, 9:24pm
 
Interestingly I was over at a ladies house today, invied over to quote for hre new kitchen electrics. Its  afalt with concrete ceiling as well with concrete floors. There will be a need to extend cooker cable (10mm) about 1 metre. As far as I am concerned I have few choices, the cable cannot be pulled, theer is no access to cable above within concrete ceiling, no access to space abve at all.

Choices are ;

(a) a junction box on the wall exposed, that wil lok really nice in the new kitchen (not!), or

(b) crimp extension test and heat shrink sleeve over each joint. Test again, insert junction into Choxbox and fit into cavity where old cooker unit was and plaster it up then it will be tiled over. If its against the regs so what, the regs would have us make peoples houses look like battleships!

Job done, one happy customer and should it ever go wrong in the future then to me thats no different to any other cable break problem.

RR
Back to top
 
Thank User For This Post  
IP Logged
 
TonyB
Newbie
*
Offline


Posts: 4


Total Thanks: 0
For This Post: 0


Gender: male

Re: Joining 10mm cooker cable
Reply #13 - May 28th, 2004, 9:35pm
 

Many thanks to all who have input on this.

Best regards,

TonyB

Smiley
Back to top
 
Thank User For This Post  
IP Logged
 
scotspark
Trade Member
*****
Offline

mmmmm it's gonna cost
you!!
Posts: 3074


Total Thanks: 10
For This Post: 0


scotland, Scotland
scotland
Scotland

Gender: male

Trade: Electrician



Re: Joining 10mm cooker cable
Reply #14 - May 29th, 2004, 8:09am
 
I would probably do the same rabbit but I doubt tony will have access to a 10mm ratchet crimper and heatshrink sleeving. Undecided

also why wire a cooker in 10mm?

I have never seen one yet that draws more load than a 6mm can safely handle domestically Kiss
Back to top
 

brown to red and blue to f****&&&&ommited!!!!!!!!!!!!!!!!!!!!!!!!!!!
Thank User For This Post View members image gallery  
IP Logged
 
rabbit_rabbit
Re: Joining 10mm cooker cable
Reply #15 - May 29th, 2004, 8:37am
 
True, true and errr .... true Scotspark.

Probably find out its only an electric oven which can be plugged in using a 13 amp plug!

RR
Back to top
 
Thank User For This Post  
IP Logged
 
The_Trician
Trade Member
*****
Offline


Posts: 7721


Total Thanks: 8
For This Post: 0


Gender: male

Trade: Electrician



Re: Joining 10mm cooker cable
Reply #16 - May 29th, 2004, 10:31am
 
For future reference - I've just bought 3 white 60A 3 terminal J/Bs from TLC - Just right for joining big sizes of T+E. - Failing this, you could use a cooker connection unit - one gang 3 terminal. Instead of connecting flex to run outside to the cooker,just join the T+E inside. You use it on a 1 gang metal box and tile round it.

TT
Back to top
 

Thats the trouble with a colostomy - you can never find the shoes to match the bag.......
Thank User For This Post  
IP Logged
 