Wiring for Hot Tub (Read 17016 times)
Jerry
Junior Member
**
Offline

I love YaBB 1G - SP1!

Posts: 11


Total Thanks: 0
For This Post: 0



Wiring for Hot Tub
Jun 27th, 2004, 8:43am
 
I'm about to have a hot tub delivered and installed in the garden. ?Before it arrives I have to provide a supply from a 32 Amp breaker through and RCD with a 4 metre SWA tail at the instalation point. ?The run from the consumer point to the location for the hot tub is about 20 metres and, with a 3 kW heater and four pumps, the start-up load of the unit will probably use a fair proportion of the 32Amp rating.

Having done most of my own house wiring and electrical instalation over the last 20 years, the thought of doing the work myself doesn't phase me. ?However, I have never installed an RCD or used SWA cable before. ?I did consider asking an electrician, but gave up because I couldn't get sensible or timely responses.

I currently have a Wylex Consumer Unit which includes a spare 30Amp breaker, but no RCD.  However, it's obsolete, so I can't get an RCD / RCBO to fit it.  I will use the existing 30Amp breaker for the supply.

My proposal is to run 6mm twin and earth from the consumer unit to a point just inside the garage where I will locate the RCD, then I will run 6mm three core SWA from the RCD for the remaining 10 metres to the hot tub. ?My questions are, is the cabling the correct size?, do I need to earth the steel wire covering of the cable as well as use one of the 3 cores as an earth back to the consumer unit earth? ?If so, should the steel wire covering be earthed to a separate earth stake (someone suggested this, but I can't see the need)? ?Do I need a special box for the RCD in order to accommodate the gland of SWA cable? ?Finally, I have a Proteus 32A, 30mA RCBO which has a black fly lead, the instructions aren't very clear - guidance on how this should be wired would be helpful. ?I assume that it goes to a point where it will connect with the neutral Line with the live Line going to the bus bar?

All advice will be gratefully received.

Note: You may be wondering why I have an RCBO.  It's because I didn't know it was different to an RCD until I got home and read the instructions by which time CEF was shut!

Jerry
Back to top
« Last Edit: Mar 7th, 2005, 7:19pm by LSpark »  
Thank User For This Post  
IP Logged
 
rabbit_rabbit
Re: Wiring for Hot Tub
Reply #1 - Jun 27th, 2004, 9:00am
 
Blimey Jerry you dont live over in Ash do you? What you describe is EXACTLY what I was doing last Thursday. My clkinet wanted a new CU prior to the tub circuit being installed and did both the same day.

Within the CU I fitted a 32 amp RCBO (30mA) on the non-RCD side of split CU. Frommthere 6.00 mm csa t/e through wall to IP junction box. From there 6.00 mm csa SWA with 4 mtr tail left near edge of tub area ready to be connected up. DO leave enough swa to get all way round tub if tub is not delivered yet.

I used 3-core swa earthed armouring and no stake.

Errr.. Proteus is sort of not good quality. Still. Most RCBO's for installation within DIN CU usually have two flying leads. One is of larger csa than the other and is to be connected to neutral bar (make sure its the right N bar). The smaller csa cable is to be connected to earth bar. Phase (live) comes in on underside (like MCB) and phase and neutral come out (to your 6.00 csa t/e) of top of RCBO and are usually or should be marked L and N.

By the way, some of the tub supplies desire an external isolator switch and for one reason only, so their service engineers can service the tub in the event that no-one is at home. My client was not impressed with that comment!

RR
Back to top
 
Thank User For This Post  
IP Logged
 
Jerry
Junior Member
**
Offline

I love YaBB 1G - SP1!

Posts: 11


Total Thanks: 0
For This Post: 0



Re: Wiring for Hot Tub
Reply #2 - Jun 27th, 2004, 9:56am
 
Thanks.  Coincidently, I used to live in Ash Vale (23 years ago).  I now live in the Midlands - pity you don't, I get you to do the job!

I assume that I wire the SWA steel wire and the core wire (used for earth) to the same earth terminal in the CU.

I can't use the RCBO in the CU as the CU is 19 years old and I can't get parts to fit (it has no RCD).  City Electrical Factors sold me a small CU to fit it in.  I could use this as the junction for the 6mm T&E and the SWA with the RCBO as an extra breaker.  However, as I already have a spare 30Amp breaker in the existing CU, it may be more sensible for me to exchange the RCBO for a simple RCD in its own box.  What do you think?

Jerry
Back to top
 
Thank User For This Post  
IP Logged
 
Lectrician
Administrator
Trade Member
Author
*****
Offline

Ask The Trades
Posts: 8814


Total Thanks: 109
For This Post: 0


Braunton, North Devon, United Kingdom
Braunton, North Devon
United Kingdom

Gender: male

Trade: Electrician



Re: Wiring for Hot Tub
Reply #3 - Jun 27th, 2004, 10:40am
 
An rcd in its own din rail box i would say, preferable a metal one so that you can gland the armour directly to that (although metal ones are harder to come by).
Back to top
 

Need to post a picture? Click HERE for info!
Thank User For This Post WWW View members image gallery  
IP Logged
 
Lectrician
Administrator
Trade Member
Author
*****
Offline

Ask The Trades
Posts: 8814


Total Thanks: 109
For This Post: 0


Braunton, North Devon, United Kingdom
Braunton, North Devon
United Kingdom

Gender: male

Trade: Electrician



Re: Wiring for Hot Tub
Reply #4 - Jun 27th, 2004, 10:40am
 
Steel armours earthed to the same point as the yellow core, onto the earth in the 6mm T+E
Back to top
 

Need to post a picture? Click HERE for info!
Thank User For This Post WWW View members image gallery  
IP Logged
 
rabbit_rabbit
Re: Wiring for Hot Tub
Reply #5 - Jun 27th, 2004, 12:29pm
 
My dear old pal Lectrician has answered well and agre with all he says.

By the way, Tubs do come under special swimming pool locations so NO control switches etc. with 2 meters of the tub. For example, if you want to install one of thsoe rotary isolation switches eventhoigh they may be IP66 or better it must NOT be installed within 2 meters of tub.

Any further queries ask away.

RR
Back to top
 
Thank User For This Post  
IP Logged
 
Jerry
Junior Member
**
Offline

I love YaBB 1G - SP1!

Posts: 11


Total Thanks: 0
For This Post: 0



Re: Wiring for Hot Tub
Reply #6 - Jun 27th, 2004, 12:58pm
 
Thanks chaps.  I know where to come with any future queries.  Never thought I'd get answers this quick.

Jerry
Back to top
 
Thank User For This Post  
IP Logged
 
rabbit_rabbit
Re: Wiring for Hot Tub
Reply #7 - Jun 27th, 2004, 3:13pm
 
Tiz a  pleasure Jerry. Hope to see you again one day!

RR
Back to top
 
Thank User For This Post  
IP Logged
 
Jerry
Junior Member
**
Offline

I love YaBB 1G - SP1!

Posts: 11


Total Thanks: 0
For This Post: 0



Re: Wiring for Hot Tub
Reply #8 - Jun 27th, 2004, 7:04pm
 
A final thought.  On looking through supplier catalogues on line, I note that there is a shortage of 32Amp 30mA RCDs.  I assume that it's OK to use a 40Amp 30mA version as the overload issue will be covered by the mini breaker in the CU?

Jerry
Back to top
 
Thank User For This Post  
IP Logged
 
Owen
Junior Member
**
Offline

I love YaBB 1G - SP1!

Posts: 7


Total Thanks: 0
For This Post: 0



Re: Wiring for Hot Tub
Reply #9 - Jun 27th, 2004, 7:13pm
 
Yes


Thats just the maximum load of the RCD. Anything over will fry it - Well, unless the MCB protects it. Which it should do: The MCB will trip long before the RCD overloads.

RCDs only check Live and Neutral imbalences, not current ammounts.
Back to top
 
Thank User For This Post  
IP Logged
 
plugwash
Administrator
*****
Offline

I love YaBB 1G - SP1!

Posts: 1383


Total Thanks: 0
For This Post: 0



Trade: Not Specified

Re: Wiring for Hot Tub
Reply #10 - Jun 27th, 2004, 9:38pm
 
yup

higher current rated rcds are more expensive to make
however haveing a wider stock range also increases expenses

so the manufactureres set up thier ranges to find the best comprimise between theese issues
Back to top
 
Thank User For This Post WWW plugwash plugwash 107767391 peter_m_green_zyworld_com plugwash  
IP Logged
 
Jerry
Junior Member
**
Offline

I love YaBB 1G - SP1!

Posts: 11


Total Thanks: 0
For This Post: 0



Re: Wiring for Hot Tub
Reply #11 - Jun 27th, 2004, 9:48pm
 
Thanks once again all.

Jerry