Add MCB
Sep 23rd, 2004, 11:08am
 
We are just getting a stair lift fitted,(for Mum),
I would like to add a seperate MCB to the existing Crabtree Starbreaker.To isolate the lift from the existing ring main. The consumer unit is next to where the socket would need to be, do I have to leave a min. dist between them? I have only used Merlin Gerin units in the past, after Isolating do I just unscrew and fold out, then clip the new MCB inplace? Sorry, 2 questions, but just found your fine site, good for out of date people like myself!
Back to top
 
Thank User For This Post  
IP Logged
 
The_Trician
Trade Member
*****
Offline


Posts: 7721


Total Thanks: 8
For This Post: 0


Gender: male

Trade: Electrician



Re: Add MCB
Reply #1 - Sep 23rd, 2004, 11:36am
 
Sounds ok to me. There isn't a regulatory value given for ther distance between a 13A socket and a Cu as far as I know.

Stair-lift supplies are usually wired like this -

13A socket to 13A plug.
13A plug to remote RCD unit.
RCD unit to stairlift wall-mounted controller.

Hope this helps.

On Stannah lifts, there's alos the chair-mounted up/down but this bit is already incorporated into the chair and shouldn't concern you.

TT
Back to top
 

Thats the trouble with a colostomy - you can never find the shoes to match the bag.......
Thank User For This Post  
IP Logged
 
plugwash
Administrator
*****
Offline

I love YaBB 1G - SP1!

Posts: 1383


Total Thanks: 0
For This Post: 0



Trade: Not Specified

Re: Add MCB
Reply #2 - Sep 23rd, 2004, 12:08pm
 
if running an individual socket from the CU best to use a 16A breaker

also this really should be on the non-rcd side don't wan't the user stuck upstairs because their faulty appliance took out the rcd

Back to top
 
Thank User For This Post WWW plugwash plugwash 107767391 peter_m_green_zyworld_com plugwash  
IP Logged
 
The_Trician
Trade Member
*****
Offline


Posts: 7721


Total Thanks: 8
For This Post: 0


Gender: male

Trade: Electrician



Re: Add MCB
Reply #3 - Sep 23rd, 2004, 12:13pm
 
Hi Plug,

The installers insist on an RCD-protected supply because believe it or not, a stairlift is classed (to them) as a portable appliance or moving machinery where there is a risk of being trapped.

That's what the Stannah engineer told me when they did one for my mum a few years ago.

They were concerned that the flexible 3 core to the moving chair bit, which rolls up and unrolls as the chair moves, might get trapped or damaged, so they fit an RCD by default mate.

TT
Back to top
 

Thats the trouble with a colostomy - you can never find the shoes to match the bag.......
Thank User For This Post  
IP Logged
 
LSpark
Global Moderator
Trade Member
Author
*****
Offline


Posts: 8069


Total Thanks: 3
For This Post: 0


London, UK, United Kingdom
London, UK
United Kingdom

Gender: male

Trade: Electrician



Re: Add MCB
Reply #4 - Sep 23rd, 2004, 1:37pm
 
Best not to assume with things like this what does and does need an RCD, always consult manufactorer or company responsible.

and having a socket next to the CU is ok, and a 16A breaker should be used as plug said.

Quote:
They were concerned that the flexible 3 core to the moving chair bit, which rolls up and unrolls as the chair moves, might get trapped or damaged, so they fit an RCD by default mate.


The ones ive seen usualy have what looks like a chainlink protective open trunking allmost, which Surrounds the flex.
Back to top
« Last Edit: Sep 23rd, 2004, 1:39pm by LSpark »  
Thank User For This Post View members image gallery  
IP Logged
 
Beanzy
Re: Add MCB
Reply #5 - Sep 23rd, 2004, 1:56pm
 
Nice and simple would be a spurred RCD protected Fused Connection Unit from the ring. That's what the neighbours had on their one. Need the Load though before could make that decision.

If seperate spur is best for you you can see if these ABB RCBOs fit in the starbreaker units. Your wholesaler may be able to let you have a look at one for comparison, if you bring one of the Starbreaker ones with you, and they'll almost cerainly be cheaper then CPC by the time carriag is taken into consideration, (a/c customers get free next day).

http://custom1.farnell.com/cpc/product.asp?catalog%5Fname=CPC+Catalogue&category...

I've used them for workshop supplies and they've been very useful.
Back to top
« Last Edit: Sep 23rd, 2004, 1:59pm by Beanzy »  
Thank User For This Post  
IP Logged
 
Hobo
Newbie
*
Offline

'Live' & Die,Off to live.

Posts: 3


Total Thanks: 0
For This Post: 0


Gender: male

Re: Add MCB
Reply #6 - Sep 23rd, 2004, 2:21pm
 
Thanks All,
Amazing help! The stairlift they are fitting is a rechargeable battery type, so I only want a seperate socket from the ring, I will fit it RCD side on a 16A. Is the clip on rail still fairly standard these days?
Back to top
 
Thank User For This Post  
IP Logged
 
Hobo
Newbie
*
Offline

'Live' & Die,Off to live.

Posts: 3


Total Thanks: 0
For This Post: 0


Gender: male

Re: Add MCB
Reply #7 - Sep 23rd, 2004, 2:25pm
 
Sorry forgot to add, the reason for not using a spur is to save making to many new channels in the wife's re-decorated walls!
Back to top
 
Thank User For This Post  
IP Logged
 
plugwash
Administrator
*****
Offline

I love YaBB 1G - SP1!

Posts: 1383


Total Thanks: 0
For This Post: 0



Trade: Not Specified

Re: Add MCB
Reply #8 - Sep 23rd, 2004, 2:29pm
 
fine rcd protection may be needed

but it should be a seperate RCD it should *NOT* be on the same rcd as the rest of the house

would you wan't a member of your family stuck upstairs with the main house rcd off and no way to get out or get help?

Back to top
 
Thank User For This Post WWW plugwash plugwash 107767391 peter_m_green_zyworld_com plugwash  
IP Logged
 
LSpark
Global Moderator
Trade Member
Author
*****
Offline


Posts: 8069


Total Thanks: 3
For This Post: 0


London, UK, United Kingdom
London, UK
United Kingdom

Gender: male

Trade: Electrician



Re: Add MCB
Reply #9 - Sep 23rd, 2004, 3:33pm
 
no certainly it should be seperate from the common RCD in the board, Should be a RCD Protected Fused Connection Unit or a RCD Protected Socket Outlet, either of them supplied from the NON Protected side of the board.

You don't need to chase out the walls if you don't want too Hobo, Use some surface trunking or simliar if it's a short distance from the board it won't look too bad

Remember to isolate the board when you decide to fit this up.
Back to top
 
Thank User For This Post View members image gallery  
IP Logged
 
The_Trician
Trade Member
*****
Offline


Posts: 7721


Total Thanks: 8
For This Post: 0


Gender: male

Trade: Electrician



Re: Add MCB
Reply #10 - Sep 23rd, 2004, 7:57pm
 
When they did my mum's they fitted 16x25 mini-trunking and a stand-alone surface-mount RCD unit - not an FCU, just a unit with L+N+E in and L+N+E out for the flex supply.

This was done by an NIC-approved contractor via Social Services.

TT
Back to top
 

Thats the trouble with a colostomy - you can never find the shoes to match the bag.......
Thank User For This Post  
IP Logged
 
supersparky
Administrator
Trade Member
Author
*****
Offline


Posts: 6097


Total Thanks: 3
For This Post: 0


Gender: male

Trade: Electrician



Re: Add MCB
Reply #11 - Sep 23rd, 2004, 8:01pm
 
something like this may be sutable?
http://homepage.ntlworld.com/john.kane10/stairlift.gif

(thanks HM)

ss
Back to top
 
Thank User For This Post WWW  
IP Logged
 
The_Trician
Trade Member
*****
Offline


Posts: 7721


Total Thanks: 8
For This Post: 0


Gender: male

Trade: Electrician



Re: Add MCB
Reply #12 - Sep 23rd, 2004, 8:08pm
 
Its a belter ss! I wonder if Thora Hird has one of those...?

TT
Back to top
 

Thats the trouble with a colostomy - you can never find the shoes to match the bag.......
Thank User For This Post  
IP Logged
 
LSpark
Global Moderator
Trade Member
Author
*****
Offline


Posts: 8069


Total Thanks: 3
For This Post: 0


London, UK, United Kingdom
London, UK
United Kingdom

Gender: male

Trade: Electrician



Re: Add MCB
Reply #13 - Sep 23rd, 2004, 9:14pm
 
haha, now come on, this is meant to be a serious post!!  Roll Eyes