Vaillant Ecotec-Honeywell T6360 PCB 2A fuse blows (Read 6507 times)
CD
GDPR opt-out









Vaillant Ecotec-Honeywell T6360 PCB 2A fuse blows
Oct 14th, 2013, 6:28pm
 
Vaillant Ecotec Pro PCB 2A slow fuse keeps blowing when I connect the Room Stat.
The Room Stat is the Honeywell T6360B.
I followed the info on 1 of your previous forums saying that
boiler terms  go to  stat terms
3                           1
4                           3
5                           2
But I've blown 4 fuses and I think the last 1 fried the board because now nothing works.
Before I at least had hot water.
I've tried 3 different stats including the old one and all the same.
Even wired the old 1 back in place & that blew out.
Any ideas would be greatly appreciated...
Back to top
 
 
IP Logged
 
Lectrician
Administrator
Trade Member
Author
*****
Offline

Ask The Trades
Posts: 8814


Total Thanks: 108
For This Post: 0


Braunton, North Devon, United Kingdom
Braunton, North Devon
United Kingdom

Gender: male

Trade: Electrician



Re: Vaillant Ecotec-Honeywell T6360 PCB 2A fuse blows
Reply #1 - Oct 14th, 2013, 6:46pm
 
Trapped wire in the wall back box?

Did the fuse only start blowing AFTER you swapped the stat? Not before?

I don't have the diagrams to hand to check the terminals. Will look later.

Have you blown the fuse in the wall isolator (FCU) for the boiler, or plug top possibly?  After one fuse blown, you should have looked for issues.....not gone on to blow four!  Lets hope te PCB is OK.....
Back to top
 

Need to post a picture? Click HERE for info!
Thank User For This Post WWW View members image gallery  
IP Logged
 
Lectrician
Administrator
Trade Member
Author
*****
Offline

Ask The Trades
Posts: 8814


Total Thanks: 108
For This Post: 0


Braunton, North Devon, United Kingdom
Braunton, North Devon
United Kingdom

Gender: male

Trade: Electrician



Re: Vaillant Ecotec-Honeywell T6360 PCB 2A fuse blows
Reply #2 - Oct 14th, 2013, 7:37pm
 
The Room Stat has connections for:

1 - LIVE IN
2 - NEUTRAL IN
3 - LIVE OUT (to fire boiler)

The boiler (by my manual):

3 - LIVE OUT
4 - LIVE IN (to fire)
5 - NEUTRAL OUT

So, what you describe in your post is correct.

However.

When I google the manual for the PRO model, Vaillants site doesnt show a 3, 4, 5 - It shows an L, N, Lr (Lr being the return to fire).  3, 4, 5 are for internal boiler wiring.

Have you a photo of your connections in the boiler?
Back to top
 

Need to post a picture? Click HERE for info!
Thank User For This Post WWW View members image gallery  
IP Logged
 
thescruff
Global Moderator
Trade Member
Author
*****
Offline

Who said plumbing was
easy.
Posts: 6037


Total Thanks: 147
For This Post: 0


Gender: male

Trade: Plumber



Re: Vaillant Ecotec-Honeywell T6360 PCB 2A fuse blows
Reply #3 - Apr 1st, 2015, 10:01pm
 
3-4-5 is fine as the OP has posted and suggests the problem is elsewhere.

5 is a spare neutral goes to 2 for the stat anticipator