Radiator With No Control Valve (Read 2011 times)
ladee
GDPR opt-out









Radiator With No Control Valve
Apr 10th, 2016, 9:54am
 
Hi, we have a Honeywell DT92E WirelessRoom Thermostat fitted downstairs in 2 storey house.
The large panel radiator in the same room is the only one in the house NOT fitted with a TVC.
We have been told there must one rad in the house left open as a safety valve in case of overheating/boiler malfunction etc.

Yesterday we came down in the morning to find the thermostat reading 25c (set at21c night before ) and the rooms unbearably hot!!
The thermo setting is still low but the rad remains very hot and actual room temp still too high and we can't control it.

We have turned the TVCs in adjacent rooms right down but need to sort this main room thermostat out.

We have a Greenstar condensing boiler on LPG.

Can anyone suggest what might be the problem ?
Back to top
 
 
IP Logged
 
Headrush
Trade Member
*****
Offline

Ask The Trades
Posts: 147


Total Thanks: 10
For This Post: 0


Nottingham, United Kingdom
Nottingham
United Kingdom

Gender: male

Trade: Plumber

Re: Radiator With No Control Valve
Reply #1 - Apr 10th, 2016, 10:03am
 
You may need to replace the batteries in the wall thermostat. When they become weak the wireless signal to the receiver at the boiler starts to fail and the heating will not switch on or off at the times or temps it's supposed to..
Back to top
 
Thank User For This Post  
IP Logged
 
thescruff
Global Moderator
Trade Member
Author
*****
Offline

Who said plumbing was
easy.
Posts: 6037


Total Thanks: 147
For This Post: 0


Gender: male

Trade: Plumber



Re: Radiator With No Control Valve
Reply #2 - Apr 10th, 2016, 10:08am
 
Hi and Welcome to ATT.

The radiator with no TRV is normal in the same room as the stat otherwise it can effect it's operation (conflict). In the old days you used a radiator (normally the bathroom) as a heat sink for the gravity circuits.

What's gone wrong ? probably not a lot, I would start by checking the batteries and re-syncing the stat with the receiver.

Do you have any motorized valves ? and what is the approximate age of the boiler etc.
Back to top
 