MICC cable to bathroom fitting. Tripping (Read 3491 times)
beekeeper21
Newbie
*
Offline

Ask The Trades
Posts: 3


Total Thanks: 0
For This Post: 0



MICC cable to bathroom fitting. Tripping
Feb 16th, 2017, 1:19pm
 
HI.

I have an ex local authority flat (built late 60's). Recently the mcb on the upstairs lighting circuit kept tripping. I traced it to the just beyond the bathroom light fitting. I had to scrape the plaster away to expose the problem. It is MICC cable coming into the two (brass?) pots. They are contained in a metal junction box and fixed in place with a metal saddle.

The issue seemed to be that one of the connections was touching the metal plate of the junction box. When moved it slightly away from the metal backplate, it would not trip (or spark), but pushing it back to the plate created a spark and tripped the circuit. I don’t see what could have ‘suddenly’ corroded. There has been no movement for at least 20 years. As I say, the fitting was buried in plaster (in the ceiling- all under artex). For now I've put some pvc sleeving around it just at the point between the brass pots and the orange sleeve where the bare copper is. Trying to trace the fitting back to the next junction would be really difficult. I'd like to solve the problem where it is. I'm tempted to insulate it with some WRMX sealant and then cover it back up. I'm aware that trying to get a MICC capable sparky with imperial fittings will be difficult. Would that be a reasonable solution? I’m surprised that it was ‘buried’ in plaster. I thought these cable connections would suck up the moisture of new plaster. Any advice gratefully received. Photo's attached.

Image 1Image 2Image 3
Image 4
Back to top
 
Thank User For This Post View members image gallery  
IP Logged
 
Lectrician
Administrator
Trade Member
Author
*****
Offline

Ask The Trades
Posts: 8814


Total Thanks: 108
For This Post: 1


Braunton, North Devon, United Kingdom
Braunton, North Devon
United Kingdom

Gender: male

Trade: Electrician



Re: MICC cable to bathroom fitting. Tripping
Reply #1 - Feb 17th, 2017, 6:42am
 
What you are suggesting is DANGEROUS, not just for that part of the lighting circuit, but the entire lighting circuit.

By moving it away from the metal box, you are breaking earth continuity (the safety conductor) and the fault can therefor not be cleared by the MCB.  The fault is still there, but as your earth is then not connected, it cannot trip the MCB.  The cable or metal box would also become live without the earth continuous!!!!!

You need to locate the fault with an insulation resistance tester, although it is likely a failed pot which requires a decent electrician to repair.  I would say rewiring this section, after locating the faulty section, is the smartest move.
Back to top
« Last Edit: Feb 17th, 2017, 6:44am by Lectrician »  

Need to post a picture? Click HERE for info!
Thank User For This Post WWW View members image gallery  
IP Logged
 
beekeeper21
Newbie
*
Offline

Ask The Trades
Posts: 3


Total Thanks: 0
For This Post: 0



Re: MICC cable to bathroom fitting. Tripping
Reply #2 - Feb 17th, 2017, 2:29pm
 
Thanks so much for this Lectician. I'm glad I asked the question. I'm trying to find an electrician who will deal with pyro. As I say I'd like to deal with the problem where it is (and probably as you say it is a failed pot). In the meantime is there something I can do to isolate that particular light fitting and make that particular connection safe but still allow the lighting circuit to operate? I imagine it may take a while to get somebody out and I'd like to use the lights in the meantime.
Back to top
 
Thank User For This Post View members image gallery  
IP Logged
 
Lectrician
Administrator
Trade Member
Author
*****
Offline

Ask The Trades
Posts: 8814


Total Thanks: 108
For This Post: 1


Braunton, North Devon, United Kingdom
Braunton, North Devon
United Kingdom

Gender: male

Trade: Electrician



Re: MICC cable to bathroom fitting. Tripping
Reply #3 - Feb 18th, 2017, 7:34am
 
The fault may not be were you have opened the ceiling.  Thats were you have split the earth, disconnected the fault which is likely further down the cable somewhere.

You need someone who can test properly with an insulation resistance test meter to locate the fault.

Why do you suspect it is at this location?  Does it only trip when you switch that light on, or at all times?  With all other lights off, does it trip?
Back to top
 

Need to post a picture? Click HERE for info!
Thank User For This Post WWW View members image gallery  
IP Logged
 
beekeeper21
Newbie
*
Offline

Ask The Trades
Posts: 3


Total Thanks: 0
For This Post: 0



Re: MICC cable to bathroom fitting. Tripping
Reply #4 - Feb 18th, 2017, 11:38am
 
Thanks again. I've got a better sense of it now. I've never encountered MICC cable before so thought it was some strange dark art that had it's own set of rules. Having done some research and thanks to your advice I'm (a bit) more clued up now. If it hadn't been pyro cable I would have maybe made different judgements.
The bottom line is that I need to just isolate the whole circuit and live without upstairs lights until I get somebody round who can do the insulations test, find the fault and if necessary work with MICC.
Hopefully I've found somebody who will come on Monday.

I'm really grateful Lectrician, you may have saved me from a frazzle!