Valliant boiler won't repressurise (Read 2362 times)
amanshu
Newbie
*
Offline

Ask The Trades
Posts: 2


Total Thanks: 0
For This Post: 0



Valliant boiler won't repressurise
Mar 3rd, 2018, 1:29pm
 
Hey all,

We have a Vaillant ecoTEC plus 831.

A couple of days ago my condensate froze over.  Annoying, but no biggie and a couple of buckets of warm water later it was working again.  I also noticed that the pressure relief pipe had a decent amount of ice under it, but didn't think anything of it at the time.

This morning the boiler turned off (halfway through my shower  Cry) and it's now reporting F22 - Dry Fire.  Checked the pressure and it's down to 0.3 bar.  Had a hunt around the house and I can't see any leaks.  I attempt to repressurise the boiler using the refill pipes and... nothing happens.  No sound of water flowing, just silence.  I bleed a couple of downstairs radiators and nothing happens.  I've checked the expansion vessel and there's definitely air in there - although I've got no way of checking the pressure on it.

Any thoughts?
Back to top
 
Thank User For This Post  
IP Logged
 
amanshu
Newbie
*
Offline

Ask The Trades
Posts: 2


Total Thanks: 0
For This Post: 0



Re: Valliant boiler won't repressurise
Reply #1 - Mar 3rd, 2018, 2:08pm
 
I've checked the refill pipe and there's definitely water flowing into it when that ends open, when I open both valves nothing comes out of the overflow pipe. The inside of the boiler is dry, so I can't see any leaks occuring there.
Back to top
 
Thank User For This Post  
IP Logged
 
Lectrician
Administrator
Trade Member
Author
*****
Offline

Ask The Trades
Posts: 8814


Total Thanks: 108
For This Post: 0


Braunton, North Devon, United Kingdom
Braunton, North Devon
United Kingdom

Gender: male

Trade: Electrician



Re: Valliant boiler won't repressurise
Reply #2 - Mar 3rd, 2018, 6:21pm
 
You should hear a flow of water as you fill, and the needle possibly spasm.
Back to top
 

Need to post a picture? Click HERE for info!
Thank User For This Post WWW View members image gallery  
IP Logged
 
thescruff
Global Moderator
Trade Member
Author
*****
Offline

Who said plumbing was
easy.
Posts: 6037


Total Thanks: 147
For This Post: 0


Gender: male

Trade: Plumber



Re: Valliant boiler won't repressurise
Reply #3 - Mar 4th, 2018, 4:50pm
 
All points to a problem with the expansion vessel. it's either lost its charge or needs replacing.

When you try to recharge it, is the water running out the PRV pipe externally.

The PRV will more than like need to be replaced, at the same time as the above.
Back to top
 