Concentric Cable Usage
Author: Lectrician


There are two main types of single phase concentric cables available. STRAIGHT CONCENTRIC and SPLIT CONCENTRIC.

STRAIGHT CONCENTRIC will not comply with BS7671! This is because the neutral is single insulated and not identified.  This type of cable is used primarily in the distribution of electricity by the electricity supply companies.

SPLIT CONCENTRIC cable will comply to BS7671.  This type of cable can be treated like standard Twin & Earth type cables.  It also offers penetration protection (A nail WILL penetrate, but will always short live to earth or neutral). It WAS often refered to in the 16th edition of BS7671 for use outside safe wiring zones. This is not the case with the 17th edition.

SPLIT CONCENTRIC cable can be terminated at consumer units, distribution boards, switch fuses and other accessories as if it was a standard PVC Twin and Earth cable.  No glands are required.




Here is a photo of 16mm² Split Concentric with only the sheath removed.  The single green and white strands are purely nylon packers - they are not conductors.

...

Here is a photo of 16mm² Split Concentric ready to be used (gently twisted neutrals, sleeved earth) - you could use one peice of large earth sleeve, but this makes the earthing conductors difficult to form.

...

Here is a photo from my camera phone (excuse quality).  This is 25mm² Split Concentric terminated into a metal clad Consumer Unit, using a standard brass bush and locknut.  The cable is cleated/clipped to the wall to give strain relief.

...

Here is a photo of some fairly rare 3 core 16mm² Split Concentric stripped and prepared.  Typically used by the DNO for TN-S supplies.

...

Here is a photo of 16mm² Straight Concentric with the sheath removed.

...

Here is a photo of 16mm² Straight Consentric ready to be used.  The CNE conductor (combined neutral and earth) is gently twisted together - no tools used.  It is best not to tighted with tools, as this can damage the crutch of the cable, and lead to a hotspot if the cable is run warm.

...

 REMEMBER  

STRAIGHT CONCENTRIC cannot be used if you are wanting to comply to BS7671!  You may use SPLIT CONCENTRIC within BS7671, and this can be treated like standard Twin & Earth type cables.  It also offers penetration protection (A nail WILL penetrate, but will always short live to earth or neutral).  It WAS often refered to in the 16th edition of BS7671 for use outside safe wiring zones.  This is not the case in the 17th edition.