Rcd trips with no cicuits powered up (Read 6009 times)
dave_jones
Newbie
*
Offline

I love YaBB 1G - SP1!

Posts: 2


Total Thanks: 0
For This Post: 0



Rcd trips with no cicuits powered up
Jun 21st, 2004, 6:38pm
 
i have just installed a split load consumer unit with rcd i have put all the lighting and smoke alarm on the non RCD side and the ring main's and shower on the RCD side of the board , i have not yet put in the ceiling roses and shower unit , though all the cable is there ready to do so , every time i power up the consumer unit (with no cicuits on) the RCD trips immediatley, i do not understand why as im sure all the wiring is correct , i also do not understand why it is tripping with nothing powered up, i know i have a protective mutiple earth (PME) can this cause this to happen or could it just be a faulty RCD
Back to top
 
Thank User For This Post  
IP Logged
 
rabbit_rabbit
Re: Rcd trips with no cicuits powered up
Reply #1 - Jun 21st, 2004, 6:46pm
 
When you say 'no circuits ON' do you mean all MCBs are in off position? If so the most likely cause is that you have a neutral-earth short somwhere. Remove each neutral from the N block and at each removal try the RCD (mind fingers!) until it locks on, the last neutral you removed is the culprit. Best of luck.

RR

If ya get to end of neutrals and it still trips THEN you have a duff RCD until then assume its OK (unless ya have an RCD tester in which test the RCD!)
Back to top
 
Thank User For This Post  
IP Logged
 
rabbit_rabbit
Re: Rcd trips with no cicuits powered up
Reply #2 - Jun 21st, 2004, 6:47pm
 
I see ya our latest member - welcome.

RR
Back to top
 
Thank User For This Post  
IP Logged
 
dave_jones
Newbie
*
Offline

I love YaBB 1G - SP1!

Posts: 2


Total Thanks: 0
For This Post: 0



Re: Rcd trips with no cicuits powered up
Reply #3 - Jun 21st, 2004, 7:11pm
 
thank you RR for your prompt reply i will do what you suggested first thing tommorow , am i right in thinking that the non RCD neutral block is the nearest one to the main switch , im just hoping i have not put all the RCD neutrals to the wrong block  Undecided as i look at the consumer unit i have a main switch with a  neutral block above it in the middle of the consumer unit i have an rcd with a  neutral block above it from this block i have a  neutral that goes directly to the bottom of the rcd
Back to top
 
Thank User For This Post  
IP Logged
 
Lectrician
Administrator
Trade Member
Author
*****
Offline

Ask The Trades
Posts: 8814


Total Thanks: 108
For This Post: 0


Braunton, North Devon, United Kingdom
Braunton, North Devon
United Kingdom

Gender: male

Trade: Electrician



Re: Rcd trips with no cicuits powered up
Reply #4 - Jun 21st, 2004, 7:14pm
 
Have seen this post several times before on other sites havn't I??  Same answer every time Smiley
Back to top
 

Need to post a picture? Click HERE for info!
Thank User For This Post WWW View members image gallery  
IP Logged
 
Lectrician
Administrator
Trade Member
Author
*****
Offline

Ask The Trades
Posts: 8814


Total Thanks: 108
For This Post: 0


Braunton, North Devon, United Kingdom
Braunton, North Devon
United Kingdom

Gender: male

Trade: Electrician



Re: Rcd trips with no cicuits powered up
Reply #5 - Jun 21st, 2004, 7:15pm
 
The main sw N Bar will have a black copper link to the main sw, the RCD one to the RCD!!  You cant get that wrong Smiley
Back to top
 

Need to post a picture? Click HERE for info!
Thank User For This Post WWW View members image gallery  
IP Logged
 
LSpark
Global Moderator
Trade Member
Author
*****
Offline


Posts: 8069


Total Thanks: 3
For This Post: 0


London, UK, United Kingdom
London, UK
United Kingdom

Gender: male

Trade: Electrician



Re: Rcd trips with no cicuits powered up
Reply #6 - Jun 21st, 2004, 10:33pm
 
problem is you can get it wrong, not personaly but for people who don't prehaps do it all time, but like lectrician said, check out all them neutrals.
Back to top
 
Thank User For This Post View members image gallery  
IP Logged
 
The_Trician
Trade Member
*****
Offline


Posts: 7721


Total Thanks: 8
For This Post: 0


Gender: male

Trade: Electrician



Re: Rcd trips with no cicuits powered up
Reply #7 - Jun 22nd, 2004, 12:38am
 
Some consumer units, even split-load ones, have a link between both Neutral bars. If you intend to use the board as a split-load item you must remove this link first.

The link is only there if you are not fitting an RCD incomer.

TT
Back to top
 

Thats the trouble with a colostomy - you can never find the shoes to match the bag.......
Thank User For This Post  
IP Logged
 
rabbit_rabbit
Re: Rcd trips with no cicuits powered up
Reply #8 - Jun 22nd, 2004, 9:01am
 
Yes you can get it wrong and I think you have answered your own question. Get them a-about-face and what your RCD is doing is saving you from yourself (only joking mate).

Depends on make but the MK Sentry split units the left N bar is non RCD and the right N bar is RCD side. And as TT says if it has a link (I have never seen one with bgut that is not to say it possible) then remove it as TT says)

RR

Back to top
 
Thank User For This Post  
IP Logged
 
LSpark
Global Moderator
Trade Member
Author
*****
Offline


Posts: 8069


Total Thanks: 3
For This Post: 0


London, UK, United Kingdom
London, UK
United Kingdom

Gender: male

Trade: Electrician



Re: Rcd trips with no cicuits powered up
Reply #9 - Jun 22nd, 2004, 1:59pm
 
you never had to get out a hack saw ray?  Tongue