earthing ?
Jul 20th, 2004, 12:21pm
 
Cheers for all the advice on DB thread. Very helpful!

One more ? for you guys. Im currently looking for an office to rent and think ive found one, but it's quite old ( nice and cheap)! but had a sparky look at the electrics , and he tells me that the  system is a bit dated! The main problem is that it has no separate earths to circuits and DB's. everything is earthed through the existing metal works, conduits etc..

sparky tells me that it's not necessarily illegal but wasn't completely sure!He said he wouldn't be able to test it properly, and he recommended some works. My question is, is it illegal or against building regulations in this day and age to work in a building which is earthed just via metal work or not. and should i take on the office, considering that i will have a few people working for me! i dont want to put anyone in danger and i dont wanna end up in court
Back to top
 
Thank User For This Post  
IP Logged
 
scotspark
Trade Member
*****
Offline

mmmmm it's gonna cost
you!!
Posts: 3074


Total Thanks: 10
For This Post: 0


scotland, Scotland
scotland
Scotland

Gender: male

Trade: Electrician



Re: earthing ?
Reply #1 - Jul 20th, 2004, 2:47pm
 
you can still use conduit and trunking as your eartg with just flying leads of back boxes. well up here in scotland anyway!! would always prefer to run seperate earth myself but can't see any reason why if your sparky has appropriate test gear he can't test the installation to see if earth is ok.

if he finds any problems you can then go to landlord as they must have buildings in sound condition if they r letting them out
Back to top
 

brown to red and blue to f****&&&&ommited!!!!!!!!!!!!!!!!!!!!!!!!!!!
Thank User For This Post View members image gallery  
IP Logged
 
LSpark
Global Moderator
Trade Member
Author
*****
Offline


Posts: 8069


Total Thanks: 3
For This Post: 0


London, UK, United Kingdom
London, UK
United Kingdom

Gender: male

Trade: Electrician



Re: earthing ?
Reply #2 - Jul 20th, 2004, 3:45pm
 
well ive no idea why he can't test it, there are severl tests for checking the earthing trough metalwork, and yes it's normal to earth trough conduit and trunking, if it's dont properly tho, it's not somthing I would be overly concerned or not, however it must be connected to earth at some point and it would be essential to check the cables at this point were correctly sized, refer the electrician to this if he comes back to you.
Back to top
« Last Edit: Jul 20th, 2004, 3:46pm by LSpark »  
Thank User For This Post View members image gallery  
IP Logged
 
jaja
Junior Member
**
Offline

I love YaBB 1G - SP1!

Posts: 6


Total Thanks: 0
For This Post: 0



Re: earthing ?
Reply #3 - Jul 20th, 2004, 4:54pm
 
So what your saying is that it's not against regulations to use metal work as earth. And as long as the system tests out ok then theres no need to install separate earths to the existing circuits?

Correct me if im wrong.
Back to top
 
Thank User For This Post  
IP Logged
 
Lectrician
Administrator
Trade Member
Author
*****
Offline

Ask The Trades
Posts: 8814


Total Thanks: 108
For This Post: 0


Braunton, North Devon, United Kingdom
Braunton, North Devon
United Kingdom

Gender: male

Trade: Electrician



Re: earthing ?
Reply #4 - Jul 20th, 2004, 5:01pm
 
Yep, no probs.  Get the Zs on the ccts tested, but i would think it would be ok.
Back to top
 

Need to post a picture? Click HERE for info!
Thank User For This Post WWW View members image gallery  
IP Logged
 
jaja
Junior Member
**
Offline

I love YaBB 1G - SP1!

Posts: 6


Total Thanks: 0
For This Post: 0



Re: earthing ?
Reply #5 - Jul 20th, 2004, 5:24pm
 
[quote author=Lectrician  link=1090322505/0#4 date=1090339316]Yep, no probs.  Get the Zs on the ccts tested, but i would think it would be ok. [/quote]

Zs CCTS??????????????????? Embarrassed
Back to top
 
Thank User For This Post  
IP Logged
 
Lectrician
Administrator
Trade Member
Author
*****
Offline

Ask The Trades
Posts: 8814


Total Thanks: 108
For This Post: 0


Braunton, North Devon, United Kingdom
Braunton, North Devon
United Kingdom

Gender: male

Trade: Electrician



Re: earthing ?
Reply #6 - Jul 20th, 2004, 5:36pm
 
Checks to ensure that the earth at the end of the circuits is suitable (and low enough) to operate fuses/mcb's that our protecting the circuit in the event of a fault.

Conduit can rust at joints, and joints can loosen, so it is important to undertake Zs at the furthest point of the conduit.  (a 25amp test is recommended.)
Back to top
 

Need to post a picture? Click HERE for info!
Thank User For This Post WWW View members image gallery  
IP Logged
 
LSpark
Global Moderator
Trade Member
Author
*****
Offline


Posts: 8069


Total Thanks: 3
For This Post: 0


London, UK, United Kingdom
London, UK
United Kingdom

Gender: male

Trade: Electrician



Re: earthing ?
Reply #7 - Jul 20th, 2004, 8:48pm
 
don't forget this is the diy section  Smiley
Back to top
 
Thank User For This Post View members image gallery  
IP Logged
 
scotspark
Trade Member
*****
Offline

mmmmm it's gonna cost
you!!
Posts: 3074


Total Thanks: 10
For This Post: 0


scotland, Scotland
scotland
Scotland

Gender: male

Trade: Electrician



Re: earthing ?
Reply #8 - Jul 20th, 2004, 9:17pm
 
yes but these are basic tests his sparky should know how to do.

have no idea why he would say he can't test to see if earhing is ok
Back to top
« Last Edit: Jul 20th, 2004, 9:17pm by scotspark »  

brown to red and blue to f****&&&&ommited!!!!!!!!!!!!!!!!!!!!!!!!!!!
Thank User For This Post View members image gallery  
IP Logged
 
LSpark
Global Moderator
Trade Member
Author
*****
Offline


Posts: 8069


Total Thanks: 3
For This Post: 0


London, UK, United Kingdom
London, UK
United Kingdom

Gender: male

Trade: Electrician



Re: earthing ?
Reply #9 - Jul 20th, 2004, 9:33pm
 
same scot  Roll Eyes
Back to top
 
Thank User For This Post View members image gallery  
IP Logged
 
Beanzy
Re: earthing ?
Reply #10 - Jul 22nd, 2004, 6:49pm
 
Only thing for spark to worry about is testing conduit if building in use or fire hazards stored near conduit. He should ideally do 'flash' insulation tests on it and it can cause problems if not done correctly. A crappy joint in the conduit may arc so you have to monitor it properly that's all really. If he's work his salt he'll be able to do it.
Back to top
 
Thank User For This Post  
IP Logged
 
ChubbyPhaseWire
Re: earthing ?
Reply #11 - Jul 22nd, 2004, 9:13pm
 
Where metallic enclosures have been used as the protective
conductors, e.g. conduit, trunking, steel-wire armouring etc the
following procedure should be followed:
(i) inspect the enclosure along its length for soundness of
construction
(ii) perform the standard ohmmeter test using the appropriate test
method described above.
Instrument: Use a low-resistance ohmmeter for this test.
Back to top
 
Thank User For This Post  
IP Logged
 
rabbit_rabbit
Re: earthing ?
Reply #12 - Jul 22nd, 2004, 9:29pm
 
Chubby!! Ya elusive character.

Ya DEAD right about the fire hazard bit. My lecturer (2391) relays a story where tests were being done on some old conduit in a flour mill (before the days where flour mills are treated same as Petro-chemical Fuel Hazards).

Anyway, out with the Megger and tests the conduit. There was one Hell of a bang in the loft as the flour dust exploded (sparks from rusty old conduit due to 500v insulation tester). The entire buidling was gutted by fire.

RR
Back to top
 
Thank User For This Post  
IP Logged
 
scotspark
Trade Member
*****
Offline

mmmmm it's gonna cost
you!!
Posts: 3074


Total Thanks: 10
For This Post: 0


scotland, Scotland
scotland
Scotland

Gender: male

Trade: Electrician



Re: earthing ?
Reply #13 - Jul 22nd, 2004, 10:49pm
 
unfortunately I doubt you will be able to visually check all of the conduit without ripping up floors n cielings.

check as much as you can tho
Back to top
 

brown to red and blue to f****&&&&ommited!!!!!!!!!!!!!!!!!!!!!!!!!!!
Thank User For This Post View members image gallery  
IP Logged
 
LSpark
Global Moderator
Trade Member
Author
*****
Offline


Posts: 8069


Total Thanks: 3
For This Post: 0


London, UK, United Kingdom
London, UK
United Kingdom

Gender: male

Trade: Electrician



Re: earthing ?
Reply #14 - Jul 22nd, 2004, 11:49pm
 
have to have the proper steel conduit for stuff like that where fire risk,explosion etc
Back to top
 
Thank User For This Post View members image gallery  
IP Logged
 
Lectrician
Administrator
Trade Member
Author
*****
Offline

Ask The Trades
Posts: 8814


Total Thanks: 108
For This Post: 0


Braunton, North Devon, United Kingdom
Braunton, North Devon
United Kingdom

Gender: male

Trade: Electrician



Re: earthing ?
Reply #15 - Jul 23rd, 2004, 7:39am
 
Solid drawn conduit for explosive atmos.
Back to top
« Last Edit: Jul 23rd, 2004, 5:31pm by Lectrician »  

Need to post a picture? Click HERE for info!
Thank User For This Post WWW View members image gallery  
IP Logged
 
LSpark
Global Moderator
Trade Member
Author
*****
Offline


Posts: 8069


Total Thanks: 3
For This Post: 0


London, UK, United Kingdom
London, UK
United Kingdom

Gender: male

Trade: Electrician



Re: earthing ?
Reply #16 - Jul 23rd, 2004, 1:04pm
 
damn ur good! Cheesy
Back to top
« Last Edit: Jul 23rd, 2004, 1:05pm by LSpark »  
Thank User For This Post View members image gallery  
IP Logged
 
Pages: 1 2 
Send Topic Print