Welcome, Guest. Please Login or Register
Welcome To Ask The Trades!
Jun 9th, 2026, 6:22pm
Quote: A verbal contract isn't worth the paper it is written on - Samuel Goldwyn


Page Index Toggle Pages: 1
Send Topic Print
Input on Rewiring (Read 7095 times)
kp1512
GDPR opt-out









Input on Rewiring
Oct 23rd, 2006, 8:34pm
 
Hi

Now that Ive sorted out my building issues with the help of the Building Forum I have comes across some electrical related issues!

One of my b uilders has an Electrician mate who was working at my house doing non-electrical stuff. HE was obserign the current installation and made some comments!

Ive just had around 70% of the house rewired with a NEW consumer unit replaced, two lighting rings replaced (US/DS) and all sockets rewired.

As well as the above, I have had fire proof Downlights put in the living room....as there currently out of there sockets due to paintings this other supposed electrician said the following whilst looking all around

a) Downlights - the connector blocks should all be covered with special blocks and nit just left exposed

Is the above true?

b) Earthing...we have 10mm Earthing going into the main consumer unit, he said this was not enough....however reading on Net I was under the impression 6mm would suffice for majority of domestic purposes?

c) Water and GAS - what earthing should these have?

d) MCB / RCD - I only have ONE rcd in the CU, and thats for the underfloor heating in the bathroom. the rest are MCB's...is this an issue? I was under the mpression RCD were for outside feeds and bathroom feeds?

e) We have an extension at side of the house....which joins the side of the kitchen. The wiring for sockets, Cooker, Extractor are all on the same ring as the extension and have to be replaced.....so basically my kitchen is on two separate rings...is this an issue?

f) Stainless Steel Switches - Earthing - the casing of the switches which are embedded in the wall are earthed..but there is NO earthing cable going into the switch plate\conntector........is this a problem? As this other psuedo electrician said its stainless steel so should b earthed!??!
Is this correct?

Can someone clarify where and why you would need a RCD?

Many thanks!!

K
Back to top
« Last Edit: Oct 23rd, 2006, 8:35pm by kp1512 »  
 
IP Logged
 
UltraSpark
GDPR opt-out









Re: Input on Rewiring
Reply #1 - Oct 23rd, 2006, 9:03pm
 
Hi,

a) Downlights - the connector blocks should all be covered with special blocks and nit just left exposed

Choc box should be used not just left exposed but in saying that I would have expected crimps and JB's instead of terminal block

Is the above true? Yes

b) Earthing...we have 10mm Earthing going into the main consumer unit, he said this was not enough....however reading on Net I was under the impression 6mm would suffice for majority of domestic purposes?

Main earth 16mm
Main Bonding 10mm to gas and water

Certain exceptions depends on earthing system

c) Water and GAS - what earthing should these have?

d) MCB / RCD - I only have ONE rcd in the CU, and thats for the underfloor heating in the bathroom. the rest are MCB's...is this an issue? I was under the mpression RCD were for outside feeds and bathroom feeds?

e) We have an extension at side of the house....which joins the side of the kitchen. The wiring for sockets, Cooker, Extractor are all on the same ring as the extension and have to be replaced.....so basically my kitchen is on two separate rings...is this an issue?

If clearly identified that sockets are on two rings for kitchen it doesnt have to be an issue.

f) Stainless Steel Switches - Earthing - the casing of the switches which are embedded in the wall are earthed..but there is NO earthing cable going into the switch plate\conntector........is this a problem? As this other psuedo electrician said its stainless steel so should b earthed!??!
Is this correct?

Yes metal switch plates should have the earth going to the earth terminal on the back of the switch plate then to the KO box.

Can someone clarify where and why you would need a RCD?

The regs say that RCD should be used on all sockets that may reasonably be expexted to supply equipment out doors.  Have you got a split load board?

Thats my thinking
Back to top
 
 
IP Logged
 
RabbitRabbit
GDPR opt-out









Re: Input on Rewiring
Reply #2 - Oct 23rd, 2006, 9:19pm
 
Quote:
a) Downlights - the connector blocks should all be covered with special blocks and nit just left exposed

Is the above true?
K


Yes it is true. All junctions should be enclosed (that includes 12 volt connections by the way as well as 230V) As stated a chocbox will do the job nicely.

Quote:
b) Earthing...we have 10mm Earthing going into the main consumer unit, he said this was not enough....however reading on Net I was under the impression 6mm would suffice for majority of domestic purposes?
K


Generally it should be 16 mm csa and as this is waht has been advised I would think the guy knows waht he is looking at (TN_S, PME, TT etc)

Quote:
c) Water and GAS - what earthing should these have?
K


Theer should be a 10mm csa cable connectng a Tenby clamp to water and gas back to the MET.

Quote:
d) MCB / RCD - I only have ONE rcd in the CU, and thats for the underfloor heating in the bathroom. the rest are MCB's...is this an issue? I was under the mpression RCD were for outside feeds and bathroom feeds?
K


As stated all sockets that can reasonably supply power to outside should be RCD protected (not a retro Reg by the way)

Quote:
e) We have an extension at side of the house....which joins the side of the kitchen. The wiring for sockets, Cooker, Extractor are all on the same ring as the extension and have to be replaced.....so basically my kitchen is on two separate rings...is this an issue?
K


Ideally (only) kitchens should be on their on final ring circuit.

Quote:
f) Stainless Steel Switches - Earthing - the casing of the switches which are embedded in the wall are earthed..but there is NO earthing cable going into the switch plate\conntector........is this a problem? As this other psuedo electrician said its stainless steel so should b earthed!??!
Is this correct?
K

Yes as stated above

Quote:
Can someone clarify where and why you would need a RCD?
K


An RCD should be used on all sockets that can reasonably be used the connect power for use outside (garden tools etc). There are other cases wheer RCD's should be used. Any permanent supply to outside (garages sheds etc) should also be  via an RCD




Back to top
 
 
IP Logged
 
kp1512
GDPR opt-out









Re: Input on Rewiring
Reply #3 - Oct 23rd, 2006, 10:18pm
 
Thanks guys!! I really appreciate both of your posts!

My Electrcians needs some words tomorrow!

I just called him and he said the main Earth cable is 20mm and the Gas and Water 10mm...but he said hell check

He said that hell take a look at the steel switches...but I also asked him about the Steel double sockets!...as they also nede to be earthed

A final question...

Ultraspark - You said the Earth should be going at the back of teh swtich and then into the KO Box?....Could you make that more Idiot averse.....sorry!....lol.....Right now the earth is screwed into the casing of the socket.......so are you saying this should go in the earth terminal at the back of the swtich and then another earth from that earth terminal to the casing box?....KO?...Im assuming is the casing box?

K
Back to top
 
 
IP Logged
 
scotspark
Trade Member
*****
Offline

mmmmm it's gonna cost
you!!
Posts: 3074


Total Thanks: 10
For This Post: 0


scotland, Scotland
scotland
Scotland

Gender: male

Trade: Electrician



Re: Input on Rewiring
Reply #4 - Oct 23rd, 2006, 10:48pm
 
as far as i am aware there is no such thing as 20mm cable??????????

the earth should go to the terminal on the back box then the terminal on the metal switch plate or vice versa.
Back to top
 

brown to red and blue to f****&&&&ommited!!!!!!!!!!!!!!!!!!!!!!!!!!!
Thank User For This Post View members image gallery  
IP Logged
 
kp1512
Re: Input on Rewiring
Reply #5 - Oct 23rd, 2006, 10:56pm
 
Scott

Bit confused....if its ONE cable within the 3 core.....so the earth....how can it go into both?.....surely id need two pieces?...or, as expected, Im being thick!
Back to top
 
Thank User For This Post  
IP Logged
 
scotspark
Trade Member
*****
Offline

mmmmm it's gonna cost
you!!
Posts: 3074


Total Thanks: 10
For This Post: 0


scotland, Scotland
scotland
Scotland

Gender: male

Trade: Electrician



Re: Input on Rewiring
Reply #6 - Oct 23rd, 2006, 11:06pm
 
the earth wire goes into the terminal on the box.


then you take another piece of wire and one end goes into the terminal on the box and  the other end goes into the terminal on the switchplate.
Back to top
 

brown to red and blue to f****&&&&ommited!!!!!!!!!!!!!!!!!!!!!!!!!!!
Thank User For This Post View members image gallery  
IP Logged
 
supersparky
Administrator
Trade Member
Author
*****
Offline


Posts: 6097


Total Thanks: 3
For This Post: 0


Gender: male

Trade: Electrician



Re: Input on Rewiring
Reply #7 - Oct 23rd, 2006, 11:25pm
 
yes im afraid your being thick  Tongue

earth wire - sleeved if twin and earth wiring to terminal one(backbox) to terminal 2 with short link (metal front plate)

however, it dosnt amtter what way arround its done

however, to confuse matters further you can take the earth from the twin and earth - or any other cable(exept 3 types of cable your unlikly to find doing the job in domestic) can go straight to the switch/ sockert and not need to earth the backbox as the need was removed for metal backboxes(k/o) with one fixed lug

again if its a metal surface box - like found in garages and workshops ect then the backbox must be earthed as it can be touched(basicly)

cable comes in the following sizes

1-(commonly lighting)
1.5-(commonly lighting)
2.5-(usualy power)
4- (usualy power and water heaters/very small showers, sheds garages ect) - ALSO IF ITS A SINGLE GREEN/YELLOW THEN THIS IS THE SIZE USED FOR CROSSBONDING baqthroom which most electricians dont understand and do it wrong)
6 - small showers and cookers/general power ect
10 - showers/cookers (ALSO WHEN IF ITS A SINGLE GREEN / YELLOW CABLE THIS SIZE OF CABLE IS USED FOR THE GAS/WATER BONDS)
16 - meter tails on small houses/flats and submains ALSO WHEN IF ITS A SINGLE GREEN / YELLOW CABLE THIS SIZE OF CABLE IS USED FOR THE MAIN EARTH TAIL
25 - Main tails on larger houses
35 - VERY VERY VERY large houses/long runs - very rare in a house situation
50 - never ever seen it in a domestic setup
and so on

obviously its a bit more involved that above and you can use smaller/larger cables and may need to use larger cables determind via some nice algerbra  :-D

but roughly above is what you could expect in a domestic
commercial is completely different but domestic is pretty much no brainer wiring

as for an rcd -
an rcd must be fitted on all sockets that may reasonably be expected to supply portable equipment outdoors
so basicly, all downstairs sockets and kitchen if its downstairs, cooker point if its downstairs and has a socket on, plus shed sockets / garage sockets / outside sockets(obviously!)

its handy to have on all sockets and showers because of the added safety but preferably not all on one - imagine the fun of finding what circuit in a bank of 20 on one rcd is faulty with no lights....

i completely disagree that its not retrospectivly enforcable in that BS7671 Is not a statutory  doccument and is only ued by everyone because it can be used to "cover ones backside" in a court of law should the poopie hit the fan and somone gets hert - if you comply with it 100% then its not actuly your fault.
it is however again different in commercial and public buildings since EAWR and HSE can and do insist on electrical maintenance and ive yet to meet a contractor who wont follow it and makes his own regs up....

anyway, back to the rcd, imagine when you sell your house or somone conducts a pir for your insurance and thers not one, whilst he cant make you have one(anymore than domesticly he can make you follow BS7671(Above mentioned arse covering doccument)) however is he going to sign your certificate and put his balls on the line to say all is well? ofcourse not!!! and you will have to have something done then or have no insurance or if selling have money nocked off by the buyer


and the moral of the story - do it by the book, the agro associated with not doing so is completely not worth it in time expence and liability!

ss
Back to top
 
Thank User For This Post WWW  
IP Logged
 
kp1512
Re: Input on Rewiring
Reply #8 - Oct 24th, 2006, 12:03am
 
Thanks guys! Detailed replies!

So in summary can I say that these two Earthing issues apply to ALL metal based Switches and Sockets? and all will require

a) Earth in sleeved 3 core direct to back box
b) another short peice made, cut and connected from the connector on switch plate to the connector on the back box

Is the above correct? Im assuming so from what you have said

K
Back to top
 
Thank User For This Post  
IP Logged
 
UltraSpark
Re: Input on Rewiring
Reply #9 - Oct 24th, 2006, 11:03am
 
Hi,

Supplymentary bonding to Knock Outs (Back Boxes) and accessories.

Socket Outlets

Usually wired using Twin and Earth.  You take the earth wire to the earth terminal on the socket outlet first.  Then using what I call a 'fly back' earth to the back box.

The same for metal decorative light switches.

Just remember outlet first back box second


This is the prefered method of bonding accessories and back box
Back to top
 
Thank User For This Post  
IP Logged
 
kp1512
Re: Input on Rewiring
Reply #10 - Oct 24th, 2006, 11:28am
 
Thanks ultra!

But just one thing, it is TWO physical cables (earthing) right?

ONE Earth in Switchplate which is in the three core, and the second is a small peice cut and then connected from the Earth on the switchplate to the back box?

K
Back to top
 
Thank User For This Post  
IP Logged
 
UltraSpark
Re: Input on Rewiring
Reply #11 - Oct 24th, 2006, 1:08pm
 
Hi Kp1512,

Yes the fly back is a seperate peice of earth wire (with green and yellow sleeving)

I think you're gettin there!

Cheers
Back to top
 
Thank User For This Post  
IP Logged
 
supersparky
Administrator
Trade Member
Author
*****
Offline


Posts: 6097


Total Thanks: 3
For This Post: 0


Gender: male

Trade: Electrician



Re: Input on Rewiring
Reply #12 - Oct 24th, 2006, 11:33pm
 
lol getting there....... Roll Eyes
Back to top
 
Thank User For This Post WWW  
IP Logged
 
kp1512
Re: Input on Rewiring
Reply #13 - Oct 26th, 2006, 12:14pm
 
Another Question! lol

RCD - it appears that its advised that you should have

Bathroom, Downstairs Sockets, Kitchen on RCDs at the minimum.

I am also led to beleive that ONE rcd takes up two slots on the CU (not sure if slots is the right answer!) for the above to occur, aside from getting a new CU, what other options have I got to ensure there all covered?

Im asking as I think my NICEIC Electrician has really messed up!!..I mean HTF do you wire a Steel Switch and NOT earth the switch plate?...Why didnt he know that the earth going into the CU needs to be 16mm?!!

Its now emerged that he hasnt bludy put in a CU big enough for the house!!!!

Oh, one thing....what is the going rate for putting in a CU (swap) for a 10-12 way CU in East London?....just to see if he really has taken the p*ss
Back to top
 
Thank User For This Post  
IP Logged
 
The_Trician
Trade Member
*****
Offline


Posts: 7721


Total Thanks: 8
For This Post: 0


Gender: male

Trade: Electrician



Re: Input on Rewiring
Reply #14 - Oct 28th, 2006, 1:09pm
 
".........you should have

Bathroom, Downstairs Sockets, Kitchen on RCDs at the minimum"


Yup, and the electric shower if you have one.


"I am also led to beleive that ONE rcd takes up two slots on the CU (not sure if slots is the right answer!) for the above to occur, aside from getting a new CU, what other options have I got to ensure there all covered?"


Yup, one double pole RCD unit takes up 2 slots. Your only other option(s) are to replace the existing CU (again!) with a larger one!

OR - depending upon the amount of room you have - fit another smaller CU alongside.

"I'm asking as I think my NICEIC Electrician has really messed up!!..I mean HTF do you wire a Steel Switch and NOT earth the switch plate?...Why didnt he know that the earth going into the CU needs to be 16mm?!!"


Just goes to show that even engaging a so-called 'Approved' or 'Registered' contractor is no guarantee of getting a good quality job done

"Its now emerged that he hasn't bloody put in a CU big enough for the house!"

I'd be looking for a free upgrade for a new replacement CU then.

As for installing a new CU - look to be paying between £300 - £500 depending upon the total number of ccts etc.

TT
Back to top
 

Thats the trouble with a colostomy - you can never find the shoes to match the bag.......
Thank User For This Post  
IP Logged
 
RabbitRabbit
Re: Input on Rewiring
Reply #15 - Oct 28th, 2006, 1:37pm
 
The_Trician wrote on Oct 28th, 2006, 1:09pm:
Just goes to show that even engaging a so-called 'Approved' or 'Registered' contractor is no guarantee of getting a good quality job done


Yup, very true indeed.

Back to top
 
Thank User For This Post  
IP Logged
 
Page Index Toggle Pages: 1
Send Topic Print