Insulation in 40 degree roof rafter using cellotex (Read 16253 times)
saaya2020
GDPR opt-out









Insulation in 40 degree roof rafter using cellotex
Jul 7th, 2013, 10:27am
 
Background: last year, we converted our Bungalow into a 2 storey house.
The Bungalow had a attic so the Roof rafters had 50mm cellotex which I was able to salvage.

When we converted to a house, the loft space was not converted into an attic. Put simply, British Gas laid 120m2 of yellow fibreglass loft insulation blanket over the horizontal floor space in my loft. The insulation is 100mm thick

My upstanding roof rafters are at 40 degrees & the dimensions are 200mm by 40mm (8 by 2's) and they are at 400mm centres. I have breathable roof felt.

My solution: In order to have proper ventilation air flow in the roof space, I know that I will need a 50mm airgap from the felt to the 50mm cellotex. Then Iam thinking to put the 100m fibreglass on top of the cellotex. Then I put foil backed plasterboard over the rafter & skim.

Is my solution ok or will I run into condensation issues? I am simply trying to re-use the existing cellotex and 120m2 fibreglss insulation.

I'd be grateful for any solution or advise to re-use this insulation rather than skip it!

Summary : 200mm rafters. So, 50mm airgap + 50mm cellotex + 100mm loft blanket. Then, foil backed plasterboard + skim.

Thanks

PS - regs not needed for this project.
Back to top
 
 
IP Logged
 
woodsmith
Global Moderator
Trade Member
Author
*****
Offline


Posts: 4395


Total Thanks: 135
For This Post: 1


Gender: male

Trade: Joiner

Re: Insulation in 40 degree roof rafter using cellotex
Reply #1 - Jul 7th, 2013, 10:05pm
 
If you look at the Tyvek website they show various insulation arrangements for pitched roofs (google Tyvek roof specifications). The way you are planning to do this looks oK to me as you plan to use foil backed plasterboard and this will act as a vapour barrier. As far as I know the gap between the felt and insulation is required so that the felt can sag in between the raters which will encourage any water that gets past the tiles to run off easily rather than as a ventilation space.
Back to top
 
Thank User For This Post View members image gallery  
IP Logged
 
saaya2020
Re: Insulation in 40 degree roof rafter using cellotex
Reply #2 - Jul 8th, 2013, 12:42am
 
thanks for the 52 page technical guide on the tyrek site. My biggest concern was the impact of having the 100mm loft blanket over the cellotex ... but the 2 key points to me seem to be 1. having an air gap between the felt and the cellotex and then 2. having foil backed plasterboard.

Started fitting the 50mm cellotex - like a jigsaw puzzle - as all the lengths are already cut. Just need to slot them inbetween the rafters. Will get some metal tape to seal the cellotex joints. It leaves a 90-100mm gap where I will put the loft blanket at the end before covering with the foil backed plasterboard.
Back to top
 
Thank User For This Post  
IP Logged
 
woodsmith
Global Moderator
Trade Member
Author
*****
Offline


Posts: 4395


Total Thanks: 135
For This Post: 1


Gender: male

Trade: Joiner

Re: Insulation in 40 degree roof rafter using cellotex
Reply #3 - Jul 8th, 2013, 7:15am
 
Yes sealing the joints in the Celotex is crucial to its performance. Getting the loft blanket to stay in place whilst you fix the plasterboard is the other challenge. I usually add a thin plastic vapour barrier which I staple to the rafters and that keeps everything in place. That way I can just use standard plasterboard. Otherwise you are probably going to need something like, thin string in a matrix or paper stapled between the rafters, to hold it in place.
Back to top
 
Thank User For This Post View members image gallery  
IP Logged
 
saaya2020
Re: Insulation in 40 degree roof rafter using cellotex
Reply #4 - Jul 8th, 2013, 9:41am
 
does it work out cheaper to fix a thin vapour barrier + normal plasterboard vs foil backed plasterboard in your opinion?

normal plasterboard 2400 x 1200 = £5
foiled plasterboard 2400 x 1200 = £10


As I've not bought anything yet, i have an opportunity to try your method.

Also, can you recommend  a good vapour barrier to attach and how mucg does it cost?

thanks
Back to top
 
Thank User For This Post  
IP Logged
 
woodsmith
Global Moderator
Trade Member
Author
*****
Offline


Posts: 4395


Total Thanks: 135
For This Post: 1


Gender: male

Trade: Joiner

Re: Insulation in 40 degree roof rafter using cellotex
Reply #5 - Jul 8th, 2013, 11:03am
 
If you go to your local builders merchant they should stock it as vapour barrier. It comes on a very big roll but I think it cost me about £15 last time I bought some. Don't let them sell you visquene damp proof membrane it is a bit too thick if you have to fold it over anywhere and its far more expensive.
Back to top
« Last Edit: Jul 8th, 2013, 11:04am by woodsmith »  
Thank User For This Post View members image gallery  
IP Logged
 
TIMBA-WOLF
Board Moderator
*****
Offline

Timba-Wolf..... Var@*sh,
should be banned!!
Posts: 7158


Total Thanks: 15
For This Post: 0


KENT,(under a tree!!!!), United Kingdom
KENT,(under a tree!!!!)
United Kingdom

Gender: male

Trade: Joiner



Re: Insulation in 40 degree roof rafter using cellotex
Reply #6 - Jul 8th, 2013, 9:33pm
 
Is there going to be  a bathroom/shower room, that will have the foil backed plasterboard you intend using, as it's ceiling??
Back to top
 

AS HONEST AND LOYAL AS THE TIMBER-WOLF. --VAR@*SH, DON'T YOU SWEAR AT ME!! PAL!!&&I DON'T SUFFER FROM INSANITY- I DAMNED WELL ENJOY IT!!!!!
Thank User For This Post View members image gallery  
IP Logged
 
saaya2020
Re: Insulation in 40 degree roof rafter using cellotex
Reply #7 - Jul 9th, 2013, 8:36am
 
No - it will only be used for storage - e.g. suitcases, tools, surplus packed foods - baked beans tins, biscuits, cereal boxes etc (i intend to make cupboards either side of the triangular space.
Back to top
 
Thank User For This Post  
IP Logged
 
Lectrician
Administrator
Trade Member
Author
*****
Offline

Ask The Trades
Posts: 8814


Total Thanks: 108
For This Post: 1


Braunton, North Devon, United Kingdom
Braunton, North Devon
United Kingdom

Gender: male

Trade: Electrician



Re: Insulation in 40 degree roof rafter using cellotex
Reply #8 - Jul 9th, 2013, 9:54pm
 
Quote:
does it work out cheaper to fix a thin vapour barrier + normal plasterboard vs foil backed plasterboard in your opinion?

Also, can you recommend  a good vapour barrier to attach and how much does it cost?


I used this stuff and for belts and braces, also foil backed board.

http://www.screwfix.com/p/vapour-barrier-2-5m-x-20m/12869
Back to top
« Last Edit: Jul 9th, 2013, 9:54pm by Lectrician »  

Need to post a picture? Click HERE for info!
Thank User For This Post WWW View members image gallery  
IP Logged
 
saaya2020
Re: Insulation in 40 degree roof rafter using cellotex
Reply #9 - Jul 10th, 2013, 1:38am
 
thanks for the link - now i know what a vapour barrier looks like! Just plastic sheeting!  How do you recommend attaching this to the rafters - maybe staples ?

thanks again
Back to top
 
Thank User For This Post  
IP Logged
 
Lectrician
Administrator
Trade Member
Author
*****
Offline

Ask The Trades
Posts: 8814


Total Thanks: 108
For This Post: 1


Braunton, North Devon, United Kingdom
Braunton, North Devon
United Kingdom

Gender: male

Trade: Electrician



Re: Insulation in 40 degree roof rafter using cellotex
Reply #10 - Jul 10th, 2013, 6:21am
 
Yep, staples.  Not many, just enough to hold it until boarding.
Back to top
 

Need to post a picture? Click HERE for info!
Thank User For This Post WWW View members image gallery  
IP Logged
 
saaya2020
Re: Insulation in 40 degree roof rafter using cellotex
Reply #11 - Jul 10th, 2013, 8:52am
 
thanks.

I have fully covered the cellotex to one side of the roof. BUT, I have realised that this new roof is a much steeper & taller roof - so I have already used up the majority the cellotex!

Ironicaly, I have 16 opened rolls the 200mm loft insulation left. Yes 16 !

Question :

Before i purchase more cellotex, i just wanted to confirm with the experts on this forum that there is no way to adapt to use the loft insulation in the roof space on its own?

Thanks



Back to top
 
Thank User For This Post  
IP Logged
 
woodsmith
Global Moderator
Trade Member
Author
*****
Offline


Posts: 4395


Total Thanks: 135
For This Post: 0


Gender: male

Trade: Joiner

Re: Insulation in 40 degree roof rafter using cellotex
Reply #12 - Jul 10th, 2013, 10:50am
 
Before Cellotex fibreglass was just stuffed between the rafters on a job like this. My own house is done that way, but Cellotex is a much better insulant in that it is more insulating, it doesn't slump, as long as you seal round the edges it is unaffected by wind blowing through it and it doesn't gradually expand filling the gap under the tiles. Plus I have bats living in my insulation, they have eaten through the Tyvek and created homes in the fibreglass I don't suppose they would have found Cellotex so inviting Roll Eyes

So you could use it,it's just a case of weighing the cost V benefits and how long you expect to live there maybe.
Back to top
 
Thank User For This Post View members image gallery  
IP Logged
 
saaya2020
Re: Insulation in 40 degree roof rafter using cellotex
Reply #13 - Jul 10th, 2013, 11:45am
 
thanks. Good Point. Yes, having converted it from a bungalow, i am definitely here for the long run! I'll need to think about this and see if i can sell on the fibreglass to make the cellotex more affordable. The 50mm sheets are £22 each. I probably will need 15 sheets as a ball park.

Bats - yikes!
Back to top
 
Thank User For This Post  
IP Logged
 
CWatters
Super Member
*****
Offline

"Daddy fick it" says James

Posts: 5150


Total Thanks: 58
For This Post: 1


Gender: male

Re: Insulation in 40 degree roof rafter using cellotex
Reply #14 - Jul 11th, 2013, 9:29am
 
I noticed you said..
Quote:
I have breathable roof felt


In which case you may not need a 50mm ventilated cavity.

In addition some makes of membrane and insulation allow the insulation to be installed in contact with the membrane. However you will probably need to allow the membrane to drape slightly between the rafters. That's to allow any water that gets past the tiles to run down the membrane under the battens. If the membrane is pushed against the battens by the insulation dirt can collect on the uphill side of the batten and eventually water can pool there as well. .

So in short you might get away with a 25mm unventilated cavity allowing another 25mm of insulation if you wanted.
Back to top
 
Thank User For This Post View members image gallery  
IP Logged
 
saaya2020
Re: Insulation in 40 degree roof rafter using cellotex
Reply #15 - Jul 11th, 2013, 3:43pm
 
Hi. My metal tape has arrived to seal the joints of the cellotex. Before i start it, i just want to clarify with this community what somebody mentioned to me:

"i should not put the loft blanket on top of the cellotex as it will create air pockets leading to condensation which in turn will make the rafters damp."

From my limited knowledge, i thought that the 50mm air gap between felt and cellotex would give enough air circulation. Plus, if I put foil backed plasterboard plus a vapour barrier as mentioned above, then that would "double" prevent the condensation - that's how i understood it!

Is my understanding correct or am i safer to not put this loft blanket over the cellotex? what do you think?

(The reason i am a little nervous is because I have seen condensation in my dad's old house. It felt like the roof was leaking in rain but it was condensation!)

Back to top
 
Thank User For This Post  
IP Logged
 
woodsmith
Global Moderator
Trade Member
Author
*****
Offline


Posts: 4395


Total Thanks: 135
For This Post: 1


Gender: male

Trade: Joiner

Re: Insulation in 40 degree roof rafter using cellotex
Reply #16 - Jul 12th, 2013, 7:31am
 
I don't think that you will have a problem as long as you have a vapour barrier (you don't need to use both foiled backed plasterboard and a plastic barrier, I would just use the plastic sheet) and you have a breathable felt.

The insulation will be more effective if you put the fibreglass between the Cellotex and the plasterboard. If you put the fibreglass on top, under the tiles, wind will be able to blow through it reducing its effectiveness.
Back to top
 