system underperforming (Read 2993 times)
JohnD
GDPR opt-out









system underperforming
Mar 2nd, 2015, 12:25am
 
Outr Church hall has a 3" single pipe system; steel 6 foot rads and original boiler went in about 1965. It is now heated by a potterton cf100 kingfisher boiler, about 12 years old. Hasn't been used that much - say about 25 - 30 hours per week at most.

All has\ worked well until 18 months ago when we noticed it was taking 3 hours to heat to a decent temprature instead of the more normal 1 1/2 hours. It now sometimes takes even longer.  The same firm that fitted it have serviced it regularly.  They said the culprit wasn't the pump as this has been checked sand it is possible the system is silted up buy rust and is probably time expired.  We have used fernox since the boiler was fitted  - however it is just possible this was not added when we had an underground leak a few years ago (under a doorway - rest of the system is above ground) and cannot  understand this unless the heat exchanger itsealf is furred up.  it does seem to us that the rads and pipework are too large to furr up easily.

To replace the boiler will cost about £2500 and the rads and pipework as well very much more. Is it possible it is the gas pressure regulator within the boiler failing? If not what could it be?  And yes, I know this is not an amateur job - we are just trying to clue ourselves in a bit as to what the problem might be.  

Regards

John Davies



Back to top
 
 
IP Logged
 
thescruff
Global Moderator
Trade Member
Author
*****
Offline

Who said plumbing was
easy.
Posts: 6037


Total Thanks: 147
For This Post: 0


Gender: male

Trade: Plumber



Re: system underperforming
Reply #1 - Mar 2nd, 2015, 9:36am
 
Is it just a single pipe with both ends or the rad connecting to the same pipe ?, some pics of the rads and connections would help.

Is the pipe much hotter than the radiators ?

What valves do you have on the radiators ?
Back to top
 
Thank User For This Post View members image gallery  
IP Logged
 
JohnD
Re: system underperforming
Reply #2 - Mar 2nd, 2015, 10:09am
 
It is indeed a single pipe with both ends of the rad connecting to the same pipe.  Obso;ete these days. Rads have been bled.

Pipes and rads are much the same temperature as far as I can tell, and each rad seem about the same temperature as the next one.

Just standard 'taps'. Haven't been touched for years.

It is probably best to put in a modern system but the cost will be colossal for the amount the place is used.

THanks for your interest

John Davies


Back to top
 
Thank User For This Post  
IP Logged
 
thescruff
Global Moderator
Trade Member
Author
*****
Offline

Who said plumbing was
easy.
Posts: 6037


Total Thanks: 147
For This Post: 0


Gender: male

Trade: Plumber



Re: system underperforming
Reply #3 - Mar 2nd, 2015, 10:33am
 
Are the pipes connected at the bottom both end or is the flow connected to the top of the rad.

I would give the pipework a good flush out with a hose pipe include the boiler, however you can't flush the rads and these will need to be taken off and flushed individually with a hosepipe outside.

You could check the pump for blockage while it's drained down.

One pipe systems are still installed commercially and works well.

Back to top
 
Thank User For This Post View members image gallery  
IP Logged
 
JohnD
Re: system underperforming
Reply #4 - Mar 2nd, 2015, 11:03pm
 
Both pipes connected to the bottom, I think.

Seems good advice - I'll pass it on to those responsible

Thanks

John Davies
Back to top
 
Thank User For This Post  
IP Logged
 
Headrush
Trade Member
*****
Offline

Ask The Trades
Posts: 147


Total Thanks: 10
For This Post: 0


Nottingham, United Kingdom
Nottingham
United Kingdom

Gender: male

Trade: Plumber

Re: system underperforming
Reply #5 - Mar 21st, 2015, 1:03pm
 
Have you checked the flow pipe from the boiler for temperature? It should be piping hot. If it's not then surely the boiler is at fault somehow. Maybe overheat stat is kicking in too early or main stat is malfunctioning..