Odd wiring question (Read 2652 times)
Ediyer
GDPR opt-out









Odd wiring question
Apr 14th, 2015, 12:19pm
 
Hi All,

This one has really confused me. I've recently moved to a new house and upon unscrewing the two light fittings to change them for newer ones (both of which work fine) in one room I've found what looks to me like they've been wired round the wrong way as the black wire has been connected to the live input on the light fitment and the red connected to the neutral. I've attached pics of each fitment to show what I mean.

Many thanks in advance
Back to top
 

Main.jpg (74 KB | 354 )
Main.jpg
 
IP Logged
 
Lectrician
Administrator
Trade Member
Author
*****
Offline

Ask The Trades
Posts: 8814


Total Thanks: 109
For This Post: 1


Braunton, North Devon, United Kingdom
Braunton, North Devon
United Kingdom

Gender: male

Trade: Electrician



Re: Odd wiring question
Reply #1 - Apr 14th, 2015, 4:20pm
 
The right hand picture looks correct EXCEPT for the brown and blue need interchanging.

Where the blue is currently connected to a single black, that black should have a small piece of red tape or sleeve to identify it as a switched live conductor.

The one on the left must have a terminal block still hiding away in the ceiling?

Both look quite messy and could do with reterminating completely.
Back to top
 

Need to post a picture? Click HERE for info!
Thank User For This Post WWW View members image gallery  
IP Logged
 
Ediyer
Re: Odd wiring question
Reply #2 - Apr 14th, 2015, 4:50pm
 
Thanks I thought as much concerning the one on the right, i'll be checking  later to confirm that is the switched live and have a root about in the ceiling on the other one to figure out what's going on there.

Out of curiosity are there any potential issues with switched live connecting to the lights neutral terminal as shown in the right picture? Or is it ok as long as the other terminal from the light is connecting to a neutral.
Back to top
 
Thank User For This Post  
IP Logged
 
Lectrician
Administrator
Trade Member
Author
*****
Offline

Ask The Trades
Posts: 8814


Total Thanks: 109
For This Post: 0


Braunton, North Devon, United Kingdom
Braunton, North Devon
United Kingdom

Gender: male

Trade: Electrician



Re: Odd wiring question
Reply #3 - Apr 14th, 2015, 5:22pm
 
Standard lights will work reverse polarity, but it is convention (and reg for certain lamp holders) that on Edison Screw types, the center pin must be the live.
Back to top
 