Mains LED Lighting. (Read 3069 times)
Dave1948
GDPR opt-out









Mains LED Lighting.
Jan 13th, 2016, 4:16pm
 
Hi, I have purchased a set of 6 x 7watt 240v LED downlighters. They have individual led drivers attached and have red and black wiring between the driver and the lamp but on the input side there are two brown wires. My question is, does this mean that there is no specific input polarity? Secondly, should I wire them in series or in parallel?

Many thanks.
Back to top
 
 
IP Logged
 
Lectrician
Administrator
Trade Member
Author
*****
Offline

Ask The Trades
Posts: 8814


Total Thanks: 108
For This Post: 1


Braunton, North Devon, United Kingdom
Braunton, North Devon
United Kingdom

Gender: male

Trade: Electrician



Re: Mains LED Lighting.
Reply #1 - Jan 13th, 2016, 6:03pm
 
They would be parallel.
If both brown, it suggest the polarity is not important.

However.

If they are both single insulated browns, and not in an outer sleeve, it suggests a cheap import - We have DOUBLE insulation on our cables.
Back to top
 

Need to post a picture? Click HERE for info!
Thank User For This Post WWW View members image gallery  
IP Logged
 
Dave1948
Re: Mains LED Lighting.
Reply #2 - Jan 13th, 2016, 7:46pm
 
Thank you Lecky, You are right that they are cheap imports and to be honest, I was a bit wary, but they do have the CE mark and are RoHS rated so I'm feeling fairly confident.

Once again, thanks for the reply.

Dave
Back to top
 
Thank User For This Post  
IP Logged
 
CWatters
Super Member
*****
Offline

"Daddy fick it" says James

Posts: 5150


Total Thanks: 58
For This Post: 1


Gender: male

Re: Mains LED Lighting.
Reply #3 - Jan 13th, 2016, 9:52pm
 
Quote:
Thank you Lecky, You are right that they are cheap imports and to be honest, I was a bit wary, but they do have the CE mark and are RoHS rated so I'm feeling fairly confident.


CE not to be confused with CE..

http://siloscordoba.com/2013/07/09/china-export-is-not-ce-a-symbol-to-cause-conf...
Back to top
 