Condensation Control Unit Mr Venty Piv System
Jan 19th, 2016, 8:23pm
 
Condensation Control Unit Mr Venty Piv System
'Eco-Loft' Positive Input Ventilation System - PIV Loft Mounted

If anybody has one of thes units I would be grateful for advice on the following questions
On the above unit there is a setting for the temperature status of above 25 degrees , above 19 degrees , and below 19 degrees . What do those settings mean ? Also a lot of people criticise these units for blowing cold air out into the area where it is installed , does the heater on them make a noticeable difference to prevent that ?
Back to top
 
Thank User For This Post  
IP Logged
 
Lectrician
Administrator
Trade Member
Author
*****
Offline

Ask The Trades
Posts: 8814


Total Thanks: 108
For This Post: 0


Braunton, North Devon, United Kingdom
Braunton, North Devon
United Kingdom

Gender: male

Trade: Electrician



Re: Condensation Control Unit Mr Venty Piv System
Reply #1 - Jan 19th, 2016, 9:05pm
 
Below 19° is standard air flow, above 19° it increases the air flow by 10%.

Above 25°, the diverter operates to bring in air from outside, not the loft.

That's how I read it anyway!

http://www.envirovent.com/product-downloads/ECO2_units_combined_user_guide_V3_LR...

http://www.envirovent.com/product-downloads/ECO2_loft_and_Twin_install_guide_V4_...