So you are fitting something 60cm wide into a 63cm gap - is this correct?
If so, this leaves you with a 1.5cm gap either side of your new extractor through which you wish to run your cable?
Most extractors have their supply cable exiting from the rear of the unit, so you'll have to chase it into the wall immediately behind the extractor. Also, for gas cookers/hobs, the extractor will need to be at least 700mm above the burners. Check the instructions which come with the extractor for more info.
|