DIY Forum >> Electrical Questions >> Gas bonding question? https://www.askthetrades.co.uk/cgi-bin/yabb/YaBB.pl?num=1244634522 Message started by starflip on Jun 10th, 2009, 12:48pm |
|
|
Title: Gas bonding question? Post by starflip on Jun 10th, 2009, 12:48pm At a property im working that needs main ex bonding doing, the gas meter is in the garage, which is seperated from the house (5m or so). So.. as you would normally take a 10mm from the met to as near the gas meter as possible, on this circumstance would you bond it within 600mm of it entering the house? any advice much appreciated. |
|
Title: Re: Gas bonding question? Post by Zambezi on Jun 10th, 2009, 12:56pm I would bond it within 600mm of where it enters the property (main house) |
|
Title: Re: Gas bonding question? Post by wozzy on Jun 10th, 2009, 9:07pm as zambs said. out of interest what route does the gas pipe take to get to the house? |
|
Title: Re: Gas bonding question? Post by starflip on Jun 10th, 2009, 9:14pm Thanks for the responce guys, the gasmain comes up in the garage which is where the meter is, out of there though the wall at waist height then along the garden wall into the house! |
|
Title: Re: Gas bonding question? Post by Lectrician on Jun 11th, 2009, 6:12am I agree - bond at point of entry to house - externally if the internal pipework is concealed. Use a blue clamp (damp environment). |
|