DIY Forum >> Electrical Questions >> Electric underfloor heating problem..
https://www.askthetrades.co.uk/cgi-bin/yabb/YaBB.pl?num=1256666203

Message started by estwing on Oct 27th, 2009, 5:56pm

Title: Electric underfloor heating problem..
Post by estwing on Oct 27th, 2009, 5:56pm

Hi all,

I installed an electric underfloor heating cable in my new bathroom in the new extension i had built last year, i did the tiling over it on the floor and swithed it on on the 16th dec 2008 and it has worked fine ever since until recently when it tripped out the 30mA 80A RCD.

I have taken every thing out that is plugged into the rcd protected curcuit (Upstairs sockets) then turned on the rcd which stays on until the thermostat for the UFH switchs it on and then it trips!!

I am an experienced joiner by trade and did the laying of the cable and the tiling myself so nothing that i can imagine that has damaged the cable, could there be another reason i am over looking?

any help here would be great..Dave....

Title: Re: Electric underfloor heating problem..
Post by sparky415 on Oct 27th, 2009, 6:49pm


Have you taken the front off the stat?
Check for crushed wires?  
Check where the cables leave the box, is there a grommet?
Then we can start getting technical  ;)

Title: Re: Electric underfloor heating problem..
Post by estwing on Oct 27th, 2009, 8:33pm


sparky415 wrote on Oct 27th, 2009, 6:49pm:
Have you taken the front off the stat?
Check for crushed wires?  
Check where the cables leave the box, is there a grommet?
Then we can start getting technical  ;)


Hi sparky
Yes taken front of stat every thing ok its a plasterboard box in ajoining bedroom built in wardrobe.
Checked all connections in stat back box even disconected floor sensor but got error msg on stat.
one point i havnt mentioned is that when i was laying out the cable i allowed for a 1000 x 800 shower tray but ended up putting a 1200 x 800 tray so theres 200 mm of over lap of the tray on the cables if you know what i mean. Slim line tray 35mm on  12mm travertine on flexi adhesive on no more ply on 22mm chipboard on 8 foot 8 x 2's
thx for your reply..dave

Title: Re: Electric underfloor heating problem..
Post by estwing on Oct 27th, 2009, 8:40pm

Also forgot to mention my electrician has moved to OZ

Title: Re: Electric underfloor heating problem..
Post by sparky415 on Oct 27th, 2009, 8:44pm

Don't blame him, lol  ::)
The next step (if you don't have a tester) is to disconnect the element wires from the stat and run the thing,
If it does not trip we know there's a problem with the heater  ;)

Title: Re: Electric underfloor heating problem..
Post by sparky415 on Oct 27th, 2009, 8:46pm

I'm half way down a bottle of red so if things start going wrong you know the reason why  ;D

Title: Re: Electric underfloor heating problem..
Post by estwing on Oct 27th, 2009, 8:53pm

Thanks for that sparky, will do that tomorrow, ive got a stinkin cold and im off to bed.

Many thx for your interest cheers, will post result tomorrow thx again...dave

Title: Re: Electric underfloor heating problem..
Post by sparky415 on Oct 27th, 2009, 9:00pm

Bugger, I forgot to say turn the power off before playing around with the electric   :-[

Have a good night!   [smiley=drink3.gif]

Title: Re: Electric underfloor heating problem..
Post by sparky415 on Oct 29th, 2009, 5:40pm

Dave!
Come back and tell us if it worked  [smiley=jumping.gif]