DIY Forum >> Electrical Questions >> Running 2 x 3 gang sockets off a consumer unit https://www.askthetrades.co.uk/cgi-bin/yabb/YaBB.pl?num=1362432440 Message started by morgaf02 on Mar 4th, 2013, 9:27pm |
|
|
Title: Running 2 x 3 gang sockets off a consumer unit Post by morgaf02 on Mar 4th, 2013, 9:27pm Im normally pretty good with electrics, but need a bit of advice. Im having some bespoke entertainment furniture installed soon and i need to rearrange the plug sockets. I was looking at running a spur off of an existing 2 gang socket but am unable to do so as the existing one is already a spur. As the consumer unit is near (under stairs cupboard) to where i want the sockets can i run 2x 3 gang sockets straight off of the consumer unit? There are spare rcd's on the unit. Any help is appreciated. Thanks. |
|
Title: Re: Running 2 x 3 gang sockets off a consumer unit Post by Lectrician on Mar 5th, 2013, 6:48pm Yes, 2.5mm² from a B20 MCB or 4mm² on a B32 MCB. These MCB's should have RCD protection. Can you take a photo of the Consumer Unit as it is? |
|
Title: Re: Running 2 x 3 gang sockets off a consumer unit Post by morgaf02 on Mar 6th, 2013, 9:43am Thanks for getting back to me. Here are a couple of pics. [album]morgaf02&1362562949[/album] |
|
Title: Re: Running 2 x 3 gang sockets off a consumer unit Post by Lectrician on Mar 6th, 2013, 5:00pm You would need to get a wylex B20 or B32 MCB and fit it to the RCD side of that board (the very far left empty way). You cannot use the B6 MCB which is empty - it is too small, and on the wrong side of the RCD. |
|
Title: Re: Running 2 x 3 gang sockets off a consumer unit Post by morgaf02 on Mar 6th, 2013, 8:01pm Thank you for the help. Much appreciated. ;D |
|