Ask The Trades | |
https://www.askthetrades.co.uk/cgi-bin/yabb/YaBB.pl
DIY Forum >> Plumbing Questions >> Air admittance valve +sub stack position https://www.askthetrades.co.uk/cgi-bin/yabb/YaBB.pl?num=1105490632 Message started by nyck on Jan 12th, 2005, 12:43am |
Title: Air admittance valve +sub stack position Post by nyck on Jan 12th, 2005, 12:43am I've had a 2 storey side extension built.in the plans i've got 2x SVP both from the garage through the floor one to the new bathroom the other to the old bathroom via a sub stack with a AAV which will be in the new bedroom not ideal. Can i put the Sub stack etc in the old bathroom and connect to the SVP in the garage with 2x 45 degree bends an bit of SVP long enough to connect the SVP in the garage and the sub in the old bathroom(hope this makes sense) or could i put the sub stack+AAV in the new bathroom I would like a few ideas before i see the BCO. thanks nyck |
Title: Re: Air admittance valve +sub stack position Post by billythekid on Jan 12th, 2005, 11:29am as long as you have a full SVP on the line somewhere the stub stack can go anywhere practical on the line. Try to avoid bends where the stack is carrying effluent and not just air wherever possible. If its easier to stick it in the bedroom, and wont be a nuisance, theres no reason it cant go there as far as I can tell, the AAV will take care of any smells/foul air that could be released, make sure you fit it properly so it doesnt stay open! smelly..... ßtk |
Ask The Trades » Powered by YaBB 2.3! YaBB © 2000-2008. All Rights Reserved. |