Title: baxi 105e instant
Post by peterdonovan on Nov 9th, 2007, 11:08pm

:-?
hi can any one give me some advice on a baxi 105e instant when i put the the heating on the pressure on the gauge goes to 3bar in about 5 minutes pressue was set at 1.5bar, then starts leaking out of the prv outside have
topped up pressure to 1.5 bar and turned the boiler off at the mains after 6 hours pressure went to 0.5 bar cant see any leaks

can any one help
thanks peter

Title: Re: baxi 105e instant
Post by thescruff on Nov 10th, 2007, 12:06am

Expansion vessel has gone by the sound of it, see pm