Message started by Natedog on Apr 7th, 2013, 8:04pm

Title: stoopid question - SWA
Post by Natedog on Apr 7th, 2013, 8:04pm

why don't they colour it red/black/green&yellow or blue/brown/green&yellow?

Title: Re: stoopid question - SWA
Post by Lectrician on Apr 7th, 2013, 8:38pm

It is designed for three phase mainly, coloured as below:
2 core : Red / Black |or| Brown / Blue
3 core : Red / Yellow / Blue |or| Brown / Black / Grey
4 core : Red / Yellow / Blue / Black |or| Brown / Black / Grey / Blue

You can get SWA in Brown / Blue / Green&Yellow, but it is VERY expensive.  You can also get a 5 core SWA with Brown / Black / Grey / Blue / Green&Yellow.