DIY Forum >> Plumbing Questions >> Low DHW flow from baxi 105E https://www.askthetrades.co.uk/cgi-bin/yabb/YaBB.pl?num=1373721263 Message started by John Barker on Jul 13th, 2013, 2:14pm |
Title: Low DHW flow from baxi 105E Post by John Barker on Jul 13th, 2013, 2:14pm Baxi 105E boiler - I have suddenly experienced low flow from my hot water taps. Temperature is very hot bot it takes forever to fill the bath. A plumber has recently removed and cleaned the heat exchanger to try and resolve this problem to no avail' Other work recently on the boler has been the renewal of the pressure vessel and also a new diaphragm has been fitted. The problem seems to have arose since the diaphragm was changed , although this may well be a coincidence any suggestions ?? |
Title: Re: Low DHW flow from baxi 105E Post by Headrush on Jul 15th, 2013, 10:41am Check the mains cold water feed valve is fully on. It only turns 90' from on to off. It's unlikely changing the diaphram would effect DHW flow rate. There's a filter built into the cold mains feed to the boiler, I once found one full of sand, might be worth checking there before all else. Turn off the valve on the cold feed or use the stopcock. Have a bowl handy to catch any residual water and undo the (from memory) chrome nut on the front of the valve, there you will see the wire filter. |