Economy 7 Storage Heaters (Read 12338 times)
Mikecork
GDPR opt-out









Economy 7 Storage Heaters
Apr 30th, 2009, 9:38am
 
I have an apartment which has Economy 7 storage heaters installed. There isn't a storage heater in the bedroom (only an electrical on-demand heater), is it possible to replace this with another Economy 7 storage heater by wiring it back to the Economy 7 RCB in the consumer unit? There are two 2.4Kw heaters in the lounge and a 1.7Kw in the hall at present. I would plan to install a 1.7Kw in the bedroom.

Thanks in advance for any help
Back to top
 
 
IP Logged
 
Zambezi
GDPR opt-out









Re: Economy 7 Storage Heaters
Reply #1 - Apr 30th, 2009, 10:05am
 
Can you give us some more details about the board feeding the other night storage heaters (NSH)? What turns the other NSH on and off (can be the E7 unit or it can be by timers)? What rating is the heater currently in your bedroom?
Back to top
 
 
IP Logged
 
Mikecork
GDPR opt-out









Re: Economy 7 Storage Heaters
Reply #2 - Apr 30th, 2009, 10:27am
 
I will have to check the capacity of the current heater and get back to you later. The Economy 7 is connected back to the central electrical cupboard for the whole block of apartments and is switched by the energy provider. In the consumer unit there is an RCB allocated for Econ 7 storage heaters.
Back to top
 
 
IP Logged
 
Lectrician
Administrator
Trade Member
Author
*****
Offline

Ask The Trades
Posts: 8815


Total Thanks: 109
For This Post: 0


Braunton, North Devon, United Kingdom
Braunton, North Devon
United Kingdom

Gender: male

Trade: Electrician



Re: Economy 7 Storage Heaters
Reply #3 - Apr 30th, 2009, 10:59am
 
I assume you have two fuseboards.  One for your usually electrical circuits, and one for your off-peak Econ 7 circuits.

If you currently have three storage rads you are likely to have 3 MCB's or fuses in the off-peak consumer unit feeding these.

There is a chance your heater in the bedroom is on it's own circuit from the 'normal' consumer unit.  If this is the case, you could easily swap that circuit from one consumer unit to the other.  If this is not the case you will need to run a new circuit from your off-peak consumer unit to your bedroom.

The only niggling thing with altering this is the RCD protection to buried cables.  I would hazard a guess that your storage heaters do not have 30mA RCD protection (just like the majority of other homes).  However, since the 17th edition of the regulations, any cables buried at a depth of less than 2" in a wall require RCD protection unless certain other criteria is met.  So, if you do alter or install a new circuit, that single circuit will require RCD protection to comply to the 17th edition.  A stupid reg, and one that causes issues with nearly every job we go to!
Back to top
 

Need to post a picture? Click HERE for info!
Thank User For This Post WWW View members image gallery  
IP Logged
 
Mikecork
Re: Economy 7 Storage Heaters
Reply #4 - Apr 30th, 2009, 4:32pm
 
Thanks for the valuable information provided to date i appreciate the inputs. The current on-demand heater in the bedroom at the moment is 1Kw.

Back to top
 
Thank User For This Post  
IP Logged
 
Y3
Re: Economy 7 Storage Heaters
Reply #5 - Apr 30th, 2009, 6:08pm
 
Lectrician wrote on Apr 30th, 2009, 10:59am:
 So, if you do alter or install a new circuit, that single circuit will require RCD protection to comply to the 17th edition.


if he has to install a new circuit for this heater, then he can do so in surface trunking to avoid the rcd. chances are the night store cu wont take todays rcbo's.
Back to top
 
Thank User For This Post  
IP Logged
 
Lectrician
Administrator
Trade Member
Author
*****
Offline

Ask The Trades
Posts: 8815


Total Thanks: 109
For This Post: 0


Braunton, North Devon, United Kingdom
Braunton, North Devon
United Kingdom

Gender: male

Trade: Electrician



Re: Economy 7 Storage Heaters
Reply #6 - Apr 30th, 2009, 7:09pm
 
An RCBO is not the only way to provide 30mA RCD protection Wink
Back to top
 

Need to post a picture? Click HERE for info!
Thank User For This Post WWW View members image gallery  
IP Logged
 
Y3
Re: Economy 7 Storage Heaters
Reply #7 - Apr 30th, 2009, 7:27pm
 
No its not, the only other way i can think of is to put an rcd enclosure in before the off peak cu, but that wouldnt comply with 17 ed in the way that all the heaters would be affected by a single fault from just one heater, meaning all source of heat lost in one go. Is there a different way lec?
Back to top
 
Thank User For This Post  
IP Logged
 
Y3
Re: Economy 7 Storage Heaters
Reply #8 - Apr 30th, 2009, 9:18pm
 
Quote:
Lectrician wrote on Apr 30th, 2009, 10:59am:
 So, if you do alter or install a new circuit, that single circuit will require RCD protection to comply to the 17th edition.


if he has to install a new circuit for this heater, then he can do so in surface trunking to avoid the rcd. chances are the night store cu wont take todays rcbo's.



I jumped the gun when i assumed that the cu for the night store would be old, its just that the majority of the ones i come across are, but this might not be the case with this scenario. An rcbo could well be used depending on the cu.
Back to top
« Last Edit: Apr 30th, 2009, 9:19pm by cosbycarl »  
Thank User For This Post  
IP Logged
 
Lectrician
Administrator
Trade Member
Author
*****
Offline

Ask The Trades
Posts: 8815


Total Thanks: 109
For This Post: 0


Braunton, North Devon, United Kingdom
Braunton, North Devon
United Kingdom

Gender: male

Trade: Electrician



Re: Economy 7 Storage Heaters
Reply #9 - Apr 30th, 2009, 9:26pm
 
Quote:
No its not, the only other way i can think of is to put an rcd enclosure in before the off peak cu, but that wouldnt comply with 17 ed in the way that all the heaters would be affected by a single fault from just one heater, meaning all source of heat lost in one go. Is there a different way lec?


How about an RCD in a seperate two mod enclosure AFTER the MCB or fuse in the CU?  As was often done to RCD protect sockets circuits when altering installs under the 16th Wink
Back to top
 

Need to post a picture? Click HERE for info!
Thank User For This Post WWW View members image gallery  
IP Logged
 
Y3
Re: Economy 7 Storage Heaters
Reply #10 - May 1st, 2009, 7:05am
 
Ahh yes, turn it into a sub-main, should of thought of that.
Back to top
 
Thank User For This Post  
IP Logged
 
Lectrician
Administrator
Trade Member
Author
*****
Offline

Ask The Trades
Posts: 8815


Total Thanks: 109
For This Post: 0


Braunton, North Devon, United Kingdom
Braunton, North Devon
United Kingdom

Gender: male

Trade: Electrician



Re: Economy 7 Storage Heaters
Reply #11 - May 1st, 2009, 7:45am
 
Quote:
Ahh yes, turn it into a sub-main, should of thought of that.


ehh?

No, I mean put an RCD in the cable between the CU and storage rad.  This is usually done beside the CU - remove the cable from the CU, place it into the RCD.  Then a new piece of cable from inside CU to the RCD.

This used to be done regularly when a customer did not want a new CU and you where fitting sockets etc.
Back to top
 

Need to post a picture? Click HERE for info!
Thank User For This Post WWW View members image gallery  
IP Logged
 
kamog
Re: Economy 7 Storage Heaters
Reply #12 - May 19th, 2009, 7:04am
 
I was thinking of adding 2 x 1.7kW storage heaters in bedroom’s in my daughter’s house and totted up the wattage of the existing 4 downstairs storage heaters plus immersion heater. Divide by 230 volts to get amps = 55.2.

Noticed no seals on anything in meter cupboard!!!! – so pulled main fuse: 60A. Taking advantage of that removed a meter tail and found it’s 7/1.70 (Have micrometer to measure unsquashed core strand)

The meter is a modern digital, says 80A

The existing storage heater consumer unit is 4-way and is full. There is room to add another 2-way cu and feed it from the tails to the 4-way via tail connector blocks but it seems to me I have to get the fuse uprated and maybe meter and tails as well.

It’s quite likely the washing m/c will be timed to come on soon after off-peak is available, unlikely but possible a late night supper in the cooker could add to the load.

I think I need some advice on loading, maybe others will be interested in this aspect..

One more query re earthing the 2-way cu (if the loading doesn’t make the extra heaters impossible): There is room to run an earth cable from the 4-way to the 2-way but I notice that earth wire for each existing cu and a water bonding all run independently back to the earth clamp on the underground cable, each having crimped tag. Is this now the only way of making earth connections – in other installations I have often seen only one earth wire running round all cu’s and occasionally use of an uninsulated earth connector block.
Back to top
 
Thank User For This Post  
IP Logged
 