May 21st, 2009, 10:21am
 
HuhHey guys I'm new to the forum. I'm Putting a new installation in to the shed. I've got a 2way Metal RCD with a 6amp Lighting And a Small Ring Final Coning Of. I've got 6mm SWA going to be run into there its only 5-6 M away from the house.

My question is where would the SWA be run into the house? would it be off a fused spur from the CCU?

any help would be appreciated thanks
Back to top
 
 
IP Logged
 
greg
GDPR opt-out









Re: SWA to a shed?
Reply #1 - May 21st, 2009, 7:49pm
 
If you search the forum, shed / garage supplies have been covered before, may answer your question.
Back to top
 
 
IP Logged
 
Y3
GDPR opt-out









Re: SWA to a shed?
Reply #2 - May 21st, 2009, 8:13pm
 
Quote:
My question is where would the SWA be run into the house? would it be off a fused spur from the CCU?

any help would be appreciated thanks


You could run it straight into your main consumer unit protected by an existing RCD or by installing an RCBO, a 20a rated MCB/RCBO respectively will be fine if your using equipment that isnt heavy in using current.

You could run it into an adaptable box external to your property, this adaptable box would have a supply from the main consumer unit using Twin & Earth cable.

You need to make sure the protective bonding conductors have been installed to the water and gas services, if they apply, before work commences.

Whats your earthing arrangement, TNS, TN-C-S, TT?

What is your shed made of? Does it have any metallic services in it i.e, water pipe?

You need to make sure your installation can handle the additional load as well.
Back to top
« Last Edit: May 21st, 2009, 9:22pm by Lectrician »  
 
IP Logged
 
baz
Trade Member
*****
Offline

If it ain't broke, keep
fixing it until it is!

Posts: 258


Total Thanks: 0
For This Post: 0


Henley-on-Thames, United Kingdom
Henley-on-Thames
United Kingdom

Gender: male

Trade: Electrician



Re: SWA to a shed?
Reply #3 - Jun 19th, 2009, 11:55pm
 
This arcticle may be of interest
http://www.theiet.org/publishing/wiring-regulations/mag/2005/16-elect-inst-outdo...

Note: its written to 16th edition.

Back to top
 

Why is it that, when we stumble across a can of worms, instead of running for the door we find ourselves reaching for a can opener?
Thank User For This Post View members image gallery  
IP Logged
 
Brunokid
Re: SWA to a shed?
Reply #4 - Jun 20th, 2009, 2:52pm
 
Quote:
You could run it straight into your main consumer unit protected by an existing RCD or by installing an RCBO, a 20a rated MCB/RCBO respectively will be fine if your using equipment that isnt heavy in using current.


Why would you need RCD protection at your CU?
Back to top
« Last Edit: Jun 21st, 2009, 6:31pm by Lectrician »  
Thank User For This Post  
IP Logged
 
Y3
Re: SWA to a shed?
Reply #5 - Jun 20th, 2009, 9:52pm
 
Quote:
Why would you need RCD protection at your CU?



Ha ha, you wouldnt if it were a TN system, however, if it was a TT system then the RCD protection would need to come from the main CU in the house, before the SWA feeding the metal CU in the shed. Whether or not thats with an existing 30mA rcd or if an RCBO needs to be fitted? Who knows?
Back to top
« Last Edit: Jun 21st, 2009, 6:32pm by Lectrician »  
Thank User For This Post  
IP Logged
 
Brunokid
Re: SWA to a shed?
Reply #6 - Jun 21st, 2009, 2:07pm
 
Whether or not thats with an existing 30mA rcd or if an RCBO needs to be fitted?

Are you sure about that? Wink
Back to top
 
Thank User For This Post  
IP Logged
 
Y3
Re: SWA to a shed?
Reply #7 - Jun 21st, 2009, 8:05pm
 
Right ok, if it's a tn system and swa is used to supply the shed then the 30mA rcd can be put in the cu in the garage or it can be added at the main cu or come from the protected side of the splitload board, he has sockets in the shed so 30mA is required. If it's a TT system with a 100mA isolator, he still needs 30mA protection for the sockets in the shed, but I see what your pointing out and I feel like a numpty for missing it, he can have the 30mA rcd in the shed as the 100mA isolator is providing fault protection for the SWA and metal enclosure.

Thanx for doing it in a polite way, I don't know what's wrong with me sometimes, maybe my brain is coming to it's end  Wink
Back to top
 
Thank User For This Post  
IP Logged
 
Lectrician
Administrator
Trade Member
Author
*****
Offline

Ask The Trades
Posts: 8815


Total Thanks: 109
For This Post: 0


Braunton, North Devon, United Kingdom
Braunton, North Devon
United Kingdom

Gender: male

Trade: Electrician



Re: SWA to a shed?
Reply #8 - Jun 21st, 2009, 8:45pm
 
Quote:
I don't know what's wrong with me sometimes, maybe my brain is coming to it's end  Wink


So soon? Smiley Grin
Back to top
« Last Edit: Jun 21st, 2009, 8:46pm by Lectrician »  

Need to post a picture? Click HERE for info!
Thank User For This Post WWW View members image gallery  
IP Logged
 
Y3
Re: SWA to a shed?
Reply #9 - Jun 21st, 2009, 9:08pm
 
I wondered when you would turn up lec  Wink

Surprised you weren't the first one to notice my error, you normally have the eye of an eagle where I'm concerned   Tongue

So soon you say? I'm now heading towards 40, I would say it was good timing!  Grin