2nd shed sub CU, main switch required? (Read 3828 times)
MikeGB
GDPR opt-out









2nd shed sub CU, main switch required?
Jun 12th, 2009, 10:03am
 
Shed 1 has 6mm swa from 40 Amp mcb (non rdc side) in house CU into shed 1 CU main 40 amp 30mA 2 pole rcd protecting all sub circuits.

32 amp mcb in shed 1 CU feeds to shed 2 via 6mm swa into 4 way enclosure with 3 ways used 2 x 6 amp and 1 x 16 amp mcb's.

Do the regs require to have a double pole means of isolation in this 2nd shed or can I just attach an "Isolate elswhere" label to the adaptable box that the swa enters the enclosure via?

I dont think it makes much difference but the sheds are right next to each other.
Back to top
 
 
IP Logged
 
Lectrician
Administrator
Trade Member
Author
*****
Offline

Ask The Trades
Posts: 8815


Total Thanks: 109
For This Post: 0


Braunton, North Devon, United Kingdom
Braunton, North Devon
United Kingdom

Gender: male

Trade: Electrician



Re: 2nd shed sub CU, main switch required?
Reply #1 - Jun 12th, 2009, 11:15am
 
It is a difficult one to call in some respects.

For the price of a dinrail mount double pole isolator, I would fit one anyway.
Back to top
 

Need to post a picture? Click HERE for info!
Thank User For This Post WWW View members image gallery  
IP Logged
 
MikeGB
Re: 2nd shed sub CU, main switch required?
Reply #2 - Jun 12th, 2009, 11:52am
 
Well if it was that simple I may have just done that Smiley but the enclosure is 4 ways (singles) so with 3 used its a case of a new enclosure as a switch will take 2 ways.
No requirement under 17th that you know of that says you must have the switch then? If so I will just go with the label.
Back to top
 
Thank User For This Post  
IP Logged
 
Y3
Re: 2nd shed sub CU, main switch required?
Reply #3 - Jun 12th, 2009, 5:48pm
 
Your point of isolation is effectively the main switch, or the 32a CB in shed one?
Back to top
« Last Edit: Jun 12th, 2009, 6:23pm by cosbycarl »  
Thank User For This Post  
IP Logged
 
MikeGB
Re: 2nd shed sub CU, main switch required?
Reply #4 - Jun 12th, 2009, 7:22pm
 
The point of isolation for shed 2 would be either via the supplying 32amp mcb in Shed 1 (live feed only) or via the main switch in Shed 1 (both poles)
Back to top
 
Thank User For This Post  
IP Logged
 