Quote:Garage feed 6mm T&E from consumers unit to sub main rcd protected @ garage will be buried in less than 50mm in wall at some stage of the run , if i sheath well can I run from main consumers unit from 40a mcb non RCD side of dual board?
If the 6mm t&e is enclosed in some kind of earthed metallic covering when buried less than 50mm in the wall, then the 40a mcb on the unprotected side will be ok, not sure how you will adequately earth steel conduit or capping if its only going to be installed for part of the run?
You could just use SWA and export the equipotential zone if there are extraneous conductive parts out in the garage. A supplimentary 10mm earth could be attached to the SWA to provide the bonding, or you can select a suitably sized SWA to act both as an Earth and Bonding conductor (I dont know how large this would have to be, as I dont have the regs to hand)