Dual Tarriff digital electricity meter (Read 7004 times)
stocksie
GDPR opt-out









Dual Tarriff digital electricity meter
Jul 10th, 2009, 9:22pm
 
Can someone enlighten me as to weather this has 2 outputs live & neutral peak and live and neutral off-peak?
Ive only ever came across an older analogue dial one which was fed of the existing meter.

Thanks lads. Grin
Back to top
 
 
IP Logged
 
Lectrician
Administrator
Trade Member
Author
*****
Offline

Ask The Trades
Posts: 8815


Total Thanks: 109
For This Post: 0


Braunton, North Devon, United Kingdom
Braunton, North Devon
United Kingdom

Gender: male

Trade: Electrician



Re: Dual Tarriff digital electricity meter
Reply #1 - Jul 10th, 2009, 9:29pm
 
There are many types these days.

Modern ones are all-in-one dual rate (or multi rate set to two rates), and have the teleswitch built in, or a programmed clock which is kept upto date via the AM sync.  This has live and neutral in, neutral out and two lives out.

Common dual rate meters have a switched neutral signal to switch them to low rate.  This is done by a teleswitch or timeclock.  The tleswitch or time clock usually also switches an 80amp off peak load too.
Back to top
 

Need to post a picture? Click HERE for info!
Thank User For This Post WWW View members image gallery  
IP Logged
 
stocksie
Re: Dual Tarriff digital electricity meter
Reply #2 - Jul 11th, 2009, 11:25am
 
Thanks for that Lec.
The job I've been asked to do is a block of 8 appartments all with night store heaters.
i was thinking a 4c 25 mm SWA from the intake/meter position to each appartment and using metal clad Switchgear and D.B's.
Can you advise if this would be the correct scenario as I cant think of another way to do it.
I wass going to mount the D.Bs in the corner of a cupboard in each appartment and come side entry into one of them and run the 2nd set of cores through to the other D.B.
Seems like more sense than having 16 SWA's in total ! Shocked
Back to top
 
Thank User For This Post  
IP Logged
 
stocksie
Re: Dual Tarriff digital electricity meter
Reply #3 - Jul 11th, 2009, 11:28am
 
Was going to use Hager aswell as they seem to do a good range of M/C for the supply/ meter end and nice looking  D.B's for the appartment end.Very cheap aswell against Wylex,crabtree etc
It's a budget job aswell....so the bloody project manager keeps telling me
Back to top
 
Thank User For This Post  
IP Logged
 
Lectrician
Administrator
Trade Member
Author
*****
Offline

Ask The Trades
Posts: 8815


Total Thanks: 109
For This Post: 0


Braunton, North Devon, United Kingdom
Braunton, North Devon
United Kingdom

Gender: male

Trade: Electrician



Re: Dual Tarriff digital electricity meter
Reply #4 - Jul 11th, 2009, 11:40am
 
Depending on the runs and where the cable will be installed in terms of depth/zoning, I would run two 16mm split concentric cables per flat.  Standard CU's in the flats, and two 60 or 80 amp switch fuses at the origin.
Back to top
« Last Edit: Jul 11th, 2009, 11:41am by Lectrician »  

Need to post a picture? Click HERE for info!
Thank User For This Post WWW View members image gallery  
IP Logged
 
stocksie
Re: Dual Tarriff digital electricity meter
Reply #5 - Jul 11th, 2009, 1:17pm
 
Why the concentrics ?Flexability of the cable?I d still have to run an earth in with them aswell though.
Not really sure as the runs as yet but SWA's wont need RCD protection whereas Concentrics will.
It's an awkward scenario whatever s used.
Would you 16 mm c ores would be enough as Xple carries over 80 Amps i know,84/6  as I recall.

Thanks
Back to top
 
Thank User For This Post  
IP Logged
 
Lectrician
Administrator
Trade Member
Author
*****
Offline

Ask The Trades
Posts: 8815


Total Thanks: 109
For This Post: 0


Braunton, North Devon, United Kingdom
Braunton, North Devon
United Kingdom

Gender: male

Trade: Electrician



Re: Dual Tarriff digital electricity meter
Reply #6 - Jul 11th, 2009, 1:29pm
 
Concentrics have a suitably sized earth conductor.  No need to supplement it.

Concentric is cheap and easy to install and temrinate.  No glands required.  Direct into a standard moulded CU and switch fuse.

No need for RCD protection if you plan the run well.  Usually in service voids and boxed in areas etc.
Back to top
 

Need to post a picture? Click HERE for info!
Thank User For This Post WWW View members image gallery  
IP Logged
 
stocksie
Re: Dual Tarriff digital electricity meter
Reply #7 - Jul 11th, 2009, 1:54pm
 
Oh right,Ive never use a one with an earth only seen them with a live and neutral.
Thanks for the guidance.
Back to top
 
Thank User For This Post  
IP Logged
 
Lectrician
Administrator
Trade Member
Author
*****
Offline

Ask The Trades
Posts: 8815


Total Thanks: 109
For This Post: 0


Braunton, North Devon, United Kingdom
Braunton, North Devon
United Kingdom

Gender: male

Trade: Electrician



Re: Dual Tarriff digital electricity meter
Reply #8 - Jul 11th, 2009, 2:19pm
 
Back to top
 

Need to post a picture? Click HERE for info!
Thank User For This Post WWW View members image gallery  
IP Logged
 
stocksie
Re: Dual Tarriff digital electricity meter
Reply #9 - Jul 11th, 2009, 2:38pm
 
Lec, thats ace thanks.
finally am I right in saying it does need RCD protection a sin the case of T+E cables?
Just spoke to the project manager and he's said the cabling will be able to be boxed in throughout.

Appreciated Cheesy
Back to top
 
Thank User For This Post  
IP Logged
 
Lectrician
Administrator
Trade Member
Author
*****
Offline

Ask The Trades
Posts: 8815


Total Thanks: 109
For This Post: 0


Braunton, North Devon, United Kingdom
Braunton, North Devon
United Kingdom

Gender: male

Trade: Electrician



Re: Dual Tarriff digital electricity meter
Reply #10 - Jul 11th, 2009, 3:14pm
 
If cables are boxed in, they are usually going to be deeper than 2" from the surface of a wall.  If this is the case, no RCD protection is required for the submains.