Lectrician
|
With a TT system, many folk will take the Ze to be the reading to the rod (rod and the MEC). They also often record a Zdb (the reading at the board with the MEC connected and all bonding and CPC's connected). This is purely for reference and not required, but useful to know. This would be called a Zdb.
Ra is the resistance of the rod, and as far as I thought could be measured with your loop tester, or the meter that no one owns!
Should the Ra box on certs be left blank if you are using a loop tester Ding?
|