Welcome, Guest. Please Login or Register
Welcome To Ask The Trades!
Apr 7th, 2026, 5:28pm
Quote: Since light travels faster than sound, some people appear bright until you hear them speak


Pages: 1 2 
Send Topic Print
RCD's TT systems (Read 15764 times)
oldspark
GDPR opt-out









RCD's TT systems
Sep 15th, 2009, 8:36pm
 
If my Zs impeadance is on the high side, will this affect the tolerances when using RCD's.
Back to top
 
 
IP Logged
 
wozzy
Trade Member
*****
Offline

Ask The Trades
Posts: 584


Total Thanks: 4
For This Post: 0


Gender: male

Trade: Electrician



Re: RCD's TT systems
Reply #1 - Sep 15th, 2009, 9:25pm
 
anything above 200 ohm is considered unstable, as far as your rcd goes the maximum i believe is 1667 ohm.  which relates to the touch voltage calculation.


Back to top
 

All advice is at least two years out of date.
Thank User For This Post View members image gallery  
IP Logged
 
dingbat
Trade Member
*****
Offline

How hard can it be?
Posts: 2822


Total Thanks: 2
For This Post: 0


Gender: male

Trade: Electrician

Re: RCD's TT systems
Reply #2 - Sep 16th, 2009, 6:24am
 
The maximum values of Zs given in table 41.5 on page 50 of BS 7671 are the maximum values to allow disconnection in the event of an earth fault on equipment. They are calculated by dividing 50V by the rating of the RCD, so (as wozzy has said) 1667 Ohms for a 30mA, 500 Ohms for a 100 mA and 167 Ohms for a 300 mA.
Back to top
 
Thank User For This Post View members image gallery  
IP Logged
 
howlingdog
Re: RCD's TT systems
Reply #3 - Sep 16th, 2009, 9:08pm
 
All above correct.  I'd  take an Ra reading at the mains end and make sure it's ok.  Then a Zdb. That way you have a starting base.  Then if the circuit readings are in the ball park then fine.  But you need to verify at the origin first.
Back to top
« Last Edit: Sep 16th, 2009, 9:09pm by howlingdog »  
Thank User For This Post  
IP Logged
 
dingbat
Trade Member
*****
Offline

How hard can it be?
Posts: 2822


Total Thanks: 2
For This Post: 0


Gender: male

Trade: Electrician

Re: RCD's TT systems
Reply #4 - Sep 16th, 2009, 9:19pm
 
Quote:
 I'd  take an Ra reading at the mains end and make sure it's ok.


Really?

Sure you wouldn't use a loop tester, like everybody else?

Quote:
Then a Zdb.


Why not just a Ze, like everybody else?

The term Zdb normally refers to a Zs value taken at the end of a sub-main, with all bonding connected.
Back to top
 
Thank User For This Post View members image gallery  
IP Logged
 
howlingdog
Re: RCD's TT systems
Reply #5 - Sep 17th, 2009, 7:53pm
 
The Ra is the 'Ze' of the rod, if you like.  On a TT there is no Ze it is called Ra.  The Zdb (Zs of the board with all bonding connected) is taken to be a base for all Zs readings of the final sub-circuits.  If the Zdb is say 5 Ohm and the final sub-circuit is say 15 Ohm then a problem will exit is the final sub-circuit.  This will not be a prob for the rcd but will show that there is a prob with the circuit wiring.
Back to top
 
Thank User For This Post  
IP Logged
 
howlingdog
Re: RCD's TT systems
Reply #6 - Sep 17th, 2009, 7:55pm
 
An Ra value may be taken with a EFLI tester or 'the other thing'.  either one will do.
Back to top
 
Thank User For This Post  
IP Logged
 
Lectrician
Administrator
Trade Member
Author
*****
Offline

Ask The Trades
Posts: 8815


Total Thanks: 109
For This Post: 0


Braunton, North Devon, United Kingdom
Braunton, North Devon
United Kingdom

Gender: male

Trade: Electrician



Re: RCD's TT systems
Reply #7 - Sep 17th, 2009, 9:16pm
 
With a TT system, many folk will take the Ze to be the reading to the rod (rod and the MEC).  They also often record a Zdb (the reading at the board with the MEC connected and all bonding and CPC's connected).  This is purely for reference and not required, but useful to know.  This would be called a Zdb.

Ra is the resistance of the rod, and as far as I thought could be measured with your loop tester, or the meter that no one owns!

Should the Ra box on certs be left blank if you are using a loop tester Ding?
Back to top
 

Need to post a picture? Click HERE for info!
Thank User For This Post WWW View members image gallery  
IP Logged
 
Y3
Re: RCD's TT systems
Reply #8 - Sep 17th, 2009, 9:23pm
 
I too thought Zdb was the term given for the EFLI being carried out at the incomer of a CU/Dist board, positioned at the end of a distribution circuit?
Back to top
 
Thank User For This Post  
IP Logged
 
Lectrician
Administrator
Trade Member
Author
*****
Offline

Ask The Trades
Posts: 8815


Total Thanks: 109
For This Post: 0


Braunton, North Devon, United Kingdom
Braunton, North Devon
United Kingdom

Gender: male

Trade: Electrician



Re: RCD's TT systems
Reply #9 - Sep 17th, 2009, 9:39pm
 
Quote:
I too thought Zdb was the term given for the EFLI being carried out at the incomer of a CU/Dist board, positioned at the end of a distribution circuit?


Or when you do not test to just the external earth......(the Ze).  If you test the main DB without disconnecting the bonding or testing directly to the MEC, you are doing a Zdb.
Back to top
 

Need to post a picture? Click HERE for info!
Thank User For This Post WWW View members image gallery  
IP Logged
 
Y3
Re: RCD's TT systems
Reply #10 - Sep 17th, 2009, 9:46pm
 
Lectrician wrote on Sep 17th, 2009, 9:39pm:
Quote:
I too thought Zdb was the term given for the EFLI being carried out at the incomer of a CU/Dist board, positioned at the end of a distribution circuit?


Or when you do not test to just the external earth......(the Ze).  If you test the main DB without disconnecting the bonding or testing directly to the MEC, you are doing a Zdb.


Where is this printed then, ive never come across this with all the reading that i do? whats MEC, Main Earth Connection?
Back to top
 
Thank User For This Post  
IP Logged
 
Lectrician
Administrator
Trade Member
Author
*****
Offline

Ask The Trades
Posts: 8815


Total Thanks: 109
For This Post: 0


Braunton, North Devon, United Kingdom
Braunton, North Devon
United Kingdom

Gender: male

Trade: Electrician



Re: RCD's TT systems
Reply #11 - Sep 17th, 2009, 10:15pm
 
It's not written anywhere, but a Ze is external.  Leave anything connected and it is no longer a Ze.

If you do a PIR and cannot isolate (this does happen), you record a Zdb at the origin, and omit dead tests.
Back to top
 

Need to post a picture? Click HERE for info!
Thank User For This Post WWW View members image gallery  
IP Logged
 
Y3
Re: RCD's TT systems
Reply #12 - Sep 17th, 2009, 11:28pm
 
Lectrician wrote on Sep 17th, 2009, 10:15pm:
It's not written anywhere, but a Ze is external.  Leave anything connected and it is no longer a Ze.

If you do a PIR and cannot isolate (this does happen), you record a Zdb at the origin, and omit dead tests.



Ok, thanx for that piss head, still able to function drunk? You are good!!   Wink
Back to top
 
Thank User For This Post  
IP Logged
 
dingbat
Trade Member
*****
Offline

How hard can it be?
Posts: 2822


Total Thanks: 2
For This Post: 0


Gender: male

Trade: Electrician

Re: RCD's TT systems
Reply #13 - Sep 18th, 2009, 4:12pm
 
Quote:
The Ra is the 'Ze' of the rod, if you like.  On a TT there is no Ze it is called Ra.


Not true.

Refer to part of Lec's answer and also to the source of all correct terminology: BS 7671

(See page 50, for a good explanation)
Back to top
« Last Edit: Sep 18th, 2009, 4:12pm by dingbat »  
Thank User For This Post View members image gallery  
IP Logged
 
dingbat
Trade Member
*****
Offline

How hard can it be?
Posts: 2822


Total Thanks: 2
For This Post: 0


Gender: male

Trade: Electrician

Re: RCD's TT systems
Reply #14 - Sep 18th, 2009, 4:19pm
 
Lectrician wrote on Sep 17th, 2009, 9:16pm:
Should the Ra box on certs be left blank if you are using a loop tester Ding?


There's no RA box if you use the Appendix 6 forms.  Wink

If you are measuring Ze, then record it as Ze on page 2; if necessary, modify the form to fit, or include an explanatory note.
Back to top
 
Thank User For This Post View members image gallery  
IP Logged
 
howlingdog
Re: RCD's TT systems
Reply #15 - Sep 23rd, 2009, 7:30pm
 
Ra is the loop path from the rod, to the tx, back through the windings, cables and back to the 'fault' that is the loop tester.  The reading is the Ra.
Back to top
 
Thank User For This Post  
IP Logged
 
Y3
Re: RCD's TT systems
Reply #16 - Sep 23rd, 2009, 9:57pm
 
Quote:
Ra is the loop path from the rod, to the tx, back through the windings, cables and back to the 'fault' that is the loop tester.  The reading is the Ra.


No it's not   Wink

Ra is the sum of the resistances of the earth electrode and the protective conductor(s) connecting it to the exposed conductive part.

Page 48 of GN3

Regards
Carl
Back to top
 
Thank User For This Post  
IP Logged
 
Pages: 1 2 
Send Topic Print