Which electrician to believe (Read 6648 times)
mikeidge
GDPR opt-out









Which electrician to believe
Nov 6th, 2009, 11:43am
 
Hi,

I've just moved house into a property that currently has a Halogen hob drawing 6.6kW. This is connected to a 6mm2 cable to a 32-amp MCB on the consumer unit, and the isolation switch for the hob in the kitchen also has a standard 13-amp socket on it.

Having just bought an oven, I'd like to get it installed. It draws a maximum of 2.35kW. I've had a number of electricians around, and I've been told they'd do one of two things:

1) Connect the oven to the existing switch and run the hob and oven off the same 32-amp MCB,
2) Give the oven its own MCB and route it straight to the consumer unit, as it's likely to trip all the time, and/or overheat.

I can't see where the existing 6mm2 cable is chased, though I'd imagine it's probably going either under the floorboards or above the ceiling. It's an older property (built in 1903), so there's solid brickwork throughout.

I'm not an electrician, so the thing I'm most wary of is how much load the existing 6mm2 cable can take given the way it's been chased. From having read about this online, it seems that at best it can take 45A, but at worst, about 35A. Surely that's a significant difference, because the hob's drawing over 28A on its own. Stick the oven into the equation, and that jumps up to 38-39A.

What also worries me is that most of the electricians failed to mention the existence of the 13-amp socket. Even without the oven, if I were to plug in a 13-amp device and use it at the same time as the hob, it'd already be drawing over 40A. That's 50A if the oven's on as well, which is definitely going to cause the circuit to trip.

My own prefered solution is to change the existing isolation switch such that it no longer has a 13-amp socket on it. It means I'll lose a socket in the kitchen, but it also means the maximum load on the cable will never exceed 39A.

What do people think about this? Would it be safe and reliable to stick the oven on the existing circuit, or should I route it straight to the consumer unit on its own cable?

(When I say "I", I mean which electrician should I go with?)

Thanks!
Back to top
 
 
IP Logged
 
big_all
Global Moderator
Trade Member
Author
*****
Offline

heeelllooo
Posts: 5596


Total Thanks: 10
For This Post: 0


Gender: male

Trade: Joiner



Re: Which electrician to believe
Reply #1 - Nov 6th, 2009, 1:43pm
 
thats where diversity comes in  it says somthing like you can allow for appliances and circuits to not be fully loaded all the time and somthing like 60% load is reasonable

after all your not going to have 4 rings a grill and oven on full blast at the same time Grin Wink

any way wait for a spark to give you the correct answer before you form an opinion

Back to top
« Last Edit: Nov 6th, 2009, 1:57pm by big_all »  

big all ---------------  we are all still learning
Thank User For This Post View members image gallery  
IP Logged
 
CWatters
Super Member
*****
Offline

"Daddy fick it" says James

Posts: 5150


Total Thanks: 58
For This Post: 0


Gender: male

Re: Which electrician to believe
Reply #2 - Nov 6th, 2009, 2:22pm
 
Did the oven come with a plug on it?

Back to top
 
Thank User For This Post View members image gallery  
IP Logged
 
londonman
Trade Member
*****
Offline

I love YaBB 1G - SP1!

Posts: 1697


Total Thanks: 13
For This Post: 0


Malvern, United Kingdom
Malvern
United Kingdom


Trade: Cabinet Maker

Re: Which electrician to believe
Reply #3 - Nov 6th, 2009, 5:25pm
 
Being pragamatic for a moment. It's your house. You know that you might exceed the capacity of the MCB if you stick a 2kW fire into the socket ...at the same time as all the hobs on and at the same time as the oven going full blast...as the others have suggested.  So don't do it!  Stick one of those child-proof covers in it if you're worried.  A lot easier than replacing and making good.
Back to top
 

Would all Third Party Apologists kindly mind their own business .....
Thank User For This Post View members image gallery  
IP Logged
 
sparky415
Trade Member
*****
Offline

Its more complicated than
I first thought
Posts: 679


Total Thanks: 0
For This Post: 0


Gender: male

Trade: Electrician



Re: Which electrician to believe
Reply #4 - Nov 6th, 2009, 6:11pm
 
Go with Number 1

It might trip on Christmas day and thats about it

(Ding, Im not even going to ask how long the run is Wink)
Back to top
 
Thank User For This Post View members image gallery  
IP Logged
 
dingbat
Trade Member
*****
Offline

How hard can it be?
Posts: 2822


Total Thanks: 2
For This Post: 0


Gender: male

Trade: Electrician

Re: Which electrician to believe
Reply #5 - Nov 6th, 2009, 6:18pm
 
big_all wrote on Nov 6th, 2009, 1:43pm:
any way wait for a spark to give you the correct answer before you form an opinion



Isn't that part of the problem?  Grin
Back to top
 
Thank User For This Post View members image gallery  
IP Logged
 
sparkyjon
Re: Which electrician to believe
Reply #6 - Dec 3rd, 2009, 9:48pm
 
unless your oven came with a 4mm cable you will have to fuse it down to 13A anyway either by a a switched fused spur or 13A socket outlet (warranty will be viod if plug removed) and upping braker to 45A will be cheapest way bare in mind local isolation (switch) needs to be present.
Back to top
 
Thank User For This Post  
IP Logged
 
supersparky
Administrator
Trade Member
Author
*****
Offline


Posts: 6097


Total Thanks: 3
For This Post: 0


Gender: male

Trade: Electrician



Re: Which electrician to believe
Reply #7 - Dec 7th, 2009, 8:28am
 
Quote:
unless your oven came with a 4mm cable you will have to fuse it down to 13A anyway either by a a switched fused spur or 13A socket outlet (warranty will be viod if plug removed) and upping braker to 45A will be cheapest way bare in mind local isolation (switch) needs to be present.



Depends on the calcs Wink

If the flex is 2.5 on the oven, maybe even 1.5 the short circuit protection will be provided by the mcb and the over current will be provided by it being a fixed appliance with fixed loading!
Back to top
 
Thank User For This Post WWW  
IP Logged
 