Problem with Baxi combi instant 105e, Please help! (Read 4806 times)
AndyAsh
GDPR opt-out









Problem with Baxi combi instant 105e, Please help!
Nov 20th, 2010, 11:36pm
 
I've got a problem with my combi boiler, ive recently had a rad off to decorate and now its all back on i cant get hot water. The pre heat function works correctly but as soon as i open a DHW tap the flame light goes out and the hot water goes luke warm then cold. Ive followed the standard stuff like checking the diaphram in the DHW differential valve and checked continuity through the microswitch all seems ok, I know its all pointing to the PCB but i was hoping someone might have a less expensive alternative to try. PS the CH is working well all air out of system etc, and pressure is holding at 1.5 bar, If you can help i will be very grateful. Cheers.
Back to top
 
 
IP Logged
 
thescruff
Global Moderator
Trade Member
Author
*****
Offline

Who said plumbing was
easy.
Posts: 6037


Total Thanks: 147
For This Post: 0


Gender: male

Trade: Plumber



Re: Problem with Baxi combi instant 105e, Please help!
Reply #1 - Nov 21st, 2010, 7:17pm
 
I can't see why anything should be broken if it worked before.  Undecided

Have you vented everything and turned all the valves on.
Back to top
 
Thank User For This Post View members image gallery  
IP Logged
 
AndyAsh
Re: Problem with Baxi combi instant 105e, Please help!
Reply #2 - Nov 21st, 2010, 9:39pm
 
ye, ive done everything i can. Ive done the fault finding in the installation manual and stop at pcb everytime, its like the boiler isnt sensing the dhw is flowing but it must be coz the neon flashes just the boiler doesnt light but if ch is on, the burner goes out. I just cant get my head round why its started playing up when it was fine before. Thanks for your reply by the way, if you can suggest trying anything else let me know, Cheers. After thought, is there some kind of thermo switch that cuts burner off when the water is hot enough and could it be stuck/knackered so the water doesnt heat up coz switch is open/closed.
Back to top
« Last Edit: Nov 21st, 2010, 9:48pm by asho40 »  
Thank User For This Post  
IP Logged
 
Lectrician
Administrator
Trade Member
Author
*****
Offline

Ask The Trades
Posts: 8815


Total Thanks: 109
For This Post: 0


Braunton, North Devon, United Kingdom
Braunton, North Devon
United Kingdom

Gender: male

Trade: Electrician



Re: Problem with Baxi combi instant 105e, Please help!
Reply #3 - Nov 21st, 2010, 9:57pm
 
Is there a bleed valve on the heat exchanger?
Back to top
 

Need to post a picture? Click HERE for info!
Thank User For This Post WWW View members image gallery  
IP Logged
 
AndyAsh
Re: Problem with Baxi combi instant 105e, Please help!
Reply #4 - Nov 22nd, 2010, 6:06pm
 
I dont think so, is it worth me havin' a look in case its air locked? The ch is working so i thought it couldnt be and i do get some DHW but only whats in the preheat.
Back to top
 
Thank User For This Post  
IP Logged
 
AndyAsh
Re: Problem with Baxi combi instant 105e, Please help!
Reply #5 - Nov 28th, 2010, 7:15pm
 
Thanks for all your help guys, ive managed to get it fixed. It was the flow switch, i put a new one on it about 3 months ago and for some unknown reason it decided to die on me again. When i arched it out the dhw worked straight away, so i fitted a new one. Im gutted i didnt check it sooner but with it being only a few months old i ruled it out from the start, it just goes to show that even new parts can be faulty! Thanks again, Andy.
Back to top
 
Thank User For This Post  
IP Logged
 