Weird Combi-Boiler pressure! (Read 2317 times)
Rob Cridland
GDPR opt-out









Weird Combi-Boiler pressure!
Nov 30th, 2010, 11:25am
 
Hi all... my first post.  Please be gentle!  Smiley

I have a Sabre combi boiler at home and the pressure at cold is around the 1 bar mark.  When the central heating is running this goes up to around 3 bar (too high!) - I suspect the expansion vessel will need repressurising, so I have that on my todo list.

However, when the central heating is on and the pressure is 3 bar, if I run a hot tap or a shower it goes down to 1.5 bar!

Could anyone be so kind as to shed some light on why this might be?

Many thanks!

Rob
Back to top
 
 
IP Logged
 
thescruff
Global Moderator
Trade Member
Author
*****
Offline

Who said plumbing was
easy.
Posts: 6037


Total Thanks: 147
For This Post: 0


Gender: male

Trade: Plumber



Re: Weird Combi-Boiler pressure!
Reply #1 - Dec 1st, 2010, 2:51am
 
One should suspect the expansion vessel as you say, but it's strange the gauge drops when you run the hot water, which suggests the hx is pin holed.

Does the pressure rise if you don't use the boiler, or fluctuate if you open and close the taps a few times.

One other possibility is you have too many rads for the size of the vessel, has any been added prior to the problem.