Replacement of heating zone-valve (Read 8296 times)
Norman Grant
GDPR opt-out









Replacement of heating zone-valve
Dec 28th, 2010, 8:45am
 
Hi, I need to replace a British Gas zone-valve-BGM VSP-2 on my hot-water circuit. Is it possible to avoid having to drain-down the system by putting bungs into my header tank as for replacing a radiator valve? Also, when it says that this kind of zone valve can be easily replaced by a Drayton(Invensys)ZA5 ,is the wiring easy to reconnect to the junction-box.Will the colour code for the wires be exactly the same ? Many Thanks.
Norman Grant
Back to top
 
 
IP Logged
 
Lectrician
Administrator
Trade Member
Author
*****
Offline

Ask The Trades
Posts: 8815


Total Thanks: 109
For This Post: 0


Braunton, North Devon, United Kingdom
Braunton, North Devon
United Kingdom

Gender: male

Trade: Electrician



Re: Replacement of heating zone-valve
Reply #1 - Dec 28th, 2010, 10:28am
 
Without a freezing kit you would need to drain.

I am not sure how you managed to swap rad valves by simply bunging the header tank TBH?

I am not familiar with the BG make, but believe they simply re-brand items as their own, so if it looks the same, chances are it is.
Back to top
 

Need to post a picture? Click HERE for info!
Thank User For This Post WWW View members image gallery  
IP Logged
 
big_all
Global Moderator
Trade Member
Author
*****
Offline

heeelllooo
Posts: 5596


Total Thanks: 10
For This Post: 0


Gender: male

Trade: Joiner



Re: Replacement of heating zone-valve
Reply #2 - Dec 28th, 2010, 11:29am
 
Lectrician wrote on Dec 28th, 2010, 10:28am:
I am not sure how you managed to swap rad valves by simply bunging the header tank TBH?



surface tension slows the water down to a dribble as the air has to replace the water
you will get water from a little bit to a lot the flow can even stop
then again being rough with the pipes can break the vacuum

the idea is you get a controlled flow a fraction off what it would be
Back to top
 

big all ---------------  we are all still learning
Thank User For This Post View members image gallery  
IP Logged
 
Norman Grant
Re: Replacement of heating zone-valve
Reply #3 - Dec 28th, 2010, 3:03pm
 
Hi,Thanks for your reply.I had watched a BRITISH gAS plumber replace my central heating zone valve without draining down and wondered if I could do thesamefor the hot water valve.He got a few pansof water but not much. Can I ask about the zone valve which I think is faulty.At present with the cold weather the central heating is on a lot and I noticed that the hot water seemed to be on a lot as well.Idiscovered that even if the hot-water was off at the controler,the hot tank remained very hot and the pipe from the zone valve to the cylinder was very hot.I took the actuator off and the spindle seemed free to move by about 45 degrees.I could see the actuator turning as I switched on and off the hot water at the conroller. I now had manual control of the zone valve but even if the spindle seemed to be definitely in the closed position, the hot water was clearly getting into the cylinder whenever the central heating is on.Is it possible for the spinle to seem to be at closed but the mechanism inside to be faulty and to be letting hot water through? This is why I want to replace the zone valve.Does this make sense? In the meantime I am running up a huge gas bill!
Thanks again for any advice.
Norman grant
Back to top
 
Thank User For This Post  
IP Logged
 
thescruff
Global Moderator
Trade Member
Author
*****
Offline

Who said plumbing was
easy.
Posts: 6037


Total Thanks: 147
For This Post: 0


Gender: male

Trade: Plumber



Re: Replacement of heating zone-valve
Reply #4 - Dec 28th, 2010, 8:11pm
 
You sure there's not a frost stat bring the boiler on.

If there is fit a pipe stat in line with the frost stat so it turns it off again when it records heat.
Back to top
 
Thank User For This Post View members image gallery  
IP Logged
 
CWatters
Super Member
*****
Offline

"Daddy fick it" says James

Posts: 5150


Total Thanks: 58
For This Post: 0


Gender: male

Re: Replacement of heating zone-valve
Reply #5 - Jan 2nd, 2011, 10:57pm
 
Quote:
the pipe from the zone valve to the cylinder was very hot..


How close is it? It's surprising how far heat from a cylinder can travel along a pipe.

Perhaps best test the valve by turning off the hot water (or disabling it) and then running the heating?