single phase contactor (Read 3893 times)
dace
GDPR opt-out









single phase contactor
Sep 12th, 2011, 9:39pm
 
contactor feeding immersion with thermostat cant stop chatting off and on, any ideas please
Back to top
 
 
IP Logged
 
CWatters
Super Member
*****
Offline

"Daddy fick it" says James

Posts: 5150


Total Thanks: 58
For This Post: 0


Gender: male

Re: single phase contactor
Reply #1 - Sep 12th, 2011, 10:59pm
 
I have no practical experience with contactors but read that chatter can be caused by low voltage. So perhaps the supply cable is too small a CSA or too long? or loose connection? eg When immersion heater turns on the voltage drops causing the contactor to drop out, immersion heater switches off, voltage rises, contactor turns on again. Repeat rapidly.

or perhaps the immersion has a high inrush current which causes the same effect (eg dipping the supply voltage). Perhaps a contactor with a longer drop out time would work? Perhaps a time delay relay in there to get past the in rush?
Back to top
« Last Edit: Sep 12th, 2011, 11:02pm by CWatters »  
Thank User For This Post View members image gallery  
IP Logged
 
Lectrician
Administrator
Trade Member
Author
*****
Offline

Ask The Trades
Posts: 8815


Total Thanks: 109
For This Post: 0


Braunton, North Devon, United Kingdom
Braunton, North Devon
United Kingdom

Gender: male

Trade: Electrician



Re: single phase contactor
Reply #2 - Sep 13th, 2011, 6:53am
 
More than likely an old dodgy contactor.
Back to top
 

Need to post a picture? Click HERE for info!
Thank User For This Post WWW View members image gallery  
IP Logged
 
sparxxxx
Full Member
***
Offline


Posts: 435


Total Thanks: 0
For This Post: 0



Re: single phase contactor
Reply #3 - Sep 14th, 2011, 6:41pm
 
Incorrect or faulty hold on circuit - contactor closes, hold on contact opens, contactor opens, hold on contact closes, contactor closes until the coil burns out.
Back to top
 
Thank User For This Post  
IP Logged
 
Lectrician
Administrator
Trade Member
Author
*****
Offline

Ask The Trades
Posts: 8815


Total Thanks: 109
For This Post: 0


Braunton, North Devon, United Kingdom
Braunton, North Devon
United Kingdom

Gender: male

Trade: Electrician



Re: single phase contactor
Reply #4 - Sep 14th, 2011, 9:02pm
 
It wouldn't be latching if just controlling an immersion heater, unless it is wired incorrectly.

I took it that this once worked and now doesn't.
Back to top
 

Need to post a picture? Click HERE for info!
Thank User For This Post WWW View members image gallery  
IP Logged
 
The_Trician
Trade Member
*****
Offline


Posts: 7721


Total Thanks: 8
For This Post: 0


Gender: male

Trade: Electrician



Re: single phase contactor
Reply #5 - Sep 14th, 2011, 10:03pm
 
If it's the thermostat wired into the control cct it could be the stat which is intermittently making & breaking.....