Which earth for a SWA armouring?
Oct 27th, 2011, 6:22pm
 
Hi
A 6mm2 2c SWA runs from the 32A MCB and RCD protected consumer unit in the property approx. 25-30mtrs to a medium size shed. The cable is to be buried and covered with tape and sand then back filled. At the shed will be a 'local' distribution board with its own RCD and MCBs feeding the lighting and up to six double sockets.
It has been suggested that at the shed end a separate earth rod should be installed to proved the main earth for the shed.

Question is..... which end of the SWA armouring should be connected to which earthing terminal - Main property, Shed end or both?
Back to top
« Last Edit: Oct 27th, 2011, 6:23pm by Flashbang »  
Thank User For This Post View members image gallery  
IP Logged
 
Lectrician
Administrator
Trade Member
Author
*****
Offline

Ask The Trades
Posts: 8815


Total Thanks: 109
For This Post: 0


Braunton, North Devon, United Kingdom
Braunton, North Devon
United Kingdom

Gender: male

Trade: Electrician



Re: Which earth for a SWA armouring?
Reply #1 - Oct 27th, 2011, 6:33pm
 
If you rod the shed, you must earth the SWA at the house end, isolating by glanding into a plastic enclosure or CU at the shed.

The SWA would be fed from a non-rcd protected way in the house.

This is only usually done with PME supplies, and even then is not strictly required unless there are extraneous conductive parts in the shed that require main protective bonding (and even then you could use 10mm SWA instead and bond them).
Back to top
 

Need to post a picture? Click HERE for info!
Thank User For This Post WWW View members image gallery  
IP Logged
 
CWatters
Super Member
*****
Offline

"Daddy fick it" says James

Posts: 5150


Total Thanks: 58
For This Post: 0


Gender: male

Re: Which earth for a SWA armouring?
Reply #2 - Oct 28th, 2011, 10:39am
 
I forget who first pointed me to this link but perhaps worth putting in the FAQ.. It redirects to a .pdf file.

http://www.google.co.uk/url?sa=t&rct=j&q=electrical%2Binstallations%2Boutdoors%2...



Back to top
« Last Edit: Oct 28th, 2011, 10:39am by CWatters »  
Thank User For This Post View members image gallery  
IP Logged
 
Flashbang
Junior Member
**
Offline

I've been P'eeeeeeed
Posts: 117


Total Thanks: 0
For This Post: 0


Gender: male



Re: Which earth for a SWA armouring?
Reply #3 - Oct 28th, 2011, 1:54pm
 
Thanks chaps.
Smiley
Back to top
 
Thank User For This Post View members image gallery  
IP Logged
 
Page Index Toggle Pages: 1
Send Topic Print