Lectrician
|
If you rod the shed, you must earth the SWA at the house end, isolating by glanding into a plastic enclosure or CU at the shed.
The SWA would be fed from a non-rcd protected way in the house.
This is only usually done with PME supplies, and even then is not strictly required unless there are extraneous conductive parts in the shed that require main protective bonding (and even then you could use 10mm SWA instead and bond them).
|