Baxi 105e Combi CH fault (only when boiler is cold (Read 7324 times)
Damoegan
GDPR opt-out









Baxi 105e Combi CH fault (only when boiler is cold
Dec 6th, 2011, 11:25pm
 
Hi Guys

I've got a very strange problem with a baxi 105e and need a little advice please.

The problem is that when the boilers is stone cold (first thing on a morning or after work on a evening) and the CH timing trys to fire up it gets a 'flame failure' fault on it..

Now, if I reset the boiler, turn on the hot tap, the boiler will fire up fine and I get hot water. If while the hot water is running I turn the CH on it will stay on! And when there is some heat in the system the CH will work from the timer just fine, until the morning or evening...

When the failure occurs (cold boiler) everything seams to work in the correct sequence, pilot rails light but go straight out!

I've replaced the CH temp sensor and DHW diaphragm in the diverter valve, still the same. I've prove out the microswitches & cleaned the combustion chamber..

Now if I go through the fault finding sequence off the Bxi pdf it points to the gas valve and/or PCB. I've sort of rueled out the gas valve as it works just fine on DHW so surely it only leaves the PCB?

Thanks in advance
Damien

ps.
I'm a fully qualified engineer (electrical and mechanical) and all gas, water and power were isolated while opening the combustion chamber...

I will not be changing any gas parts myself, I'm just trying to get a handle on what the problem could be.

Thanks

Back to top
 
 
IP Logged
 
Damoegan
GDPR opt-out









Re: Baxi 105e Combi CH fault (only when boiler is cold
Reply #1 - Dec 7th, 2011, 8:50am
 
Any thoughts guys?
Back to top
 
 
IP Logged
 
TIMBA-WOLF
Board Moderator
*****
Offline

Timba-Wolf..... Var@*sh,
should be banned!!
Posts: 7158


Total Thanks: 15
For This Post: 0


KENT,(under a tree!!!!), United Kingdom
KENT,(under a tree!!!!)
United Kingdom

Gender: male

Trade: Joiner



Re: Baxi 105e Combi CH fault (only when boiler is cold
Reply #2 - Dec 7th, 2011, 12:29pm
 
Scruff, where are you!!!
Back to top
 

AS HONEST AND LOYAL AS THE TIMBER-WOLF. --VAR@*SH, DON'T YOU SWEAR AT ME!! PAL!!&&I DON'T SUFFER FROM INSANITY- I DAMNED WELL ENJOY IT!!!!!
Thank User For This Post View members image gallery  
IP Logged
 
thescruff
Global Moderator
Trade Member
Author
*****
Offline

Who said plumbing was
easy.
Posts: 6037


Total Thanks: 147
For This Post: 0


Gender: male

Trade: Plumber



Re: Baxi 105e Combi CH fault (only when boiler is cold
Reply #3 - Dec 7th, 2011, 4:48pm
 
No idea Wolfie  Kiss

Sounds like something is sticking when the boiler is cold, could be the gas valve, pump perhaps.

Needs an RGI to look at it when the boiler is cold, and hopefully he'll put his finger on it straight away.
Back to top
 
Thank User For This Post View members image gallery  
IP Logged
 
Damoegan
Re: Baxi 105e Combi CH fault (only when boiler is cold
Reply #4 - Dec 7th, 2011, 5:30pm
 
Damn, I thought you guys would know what it was straight off the top of your head Wink
Back to top
 
Thank User For This Post  
IP Logged
 
thescruff
Global Moderator
Trade Member
Author
*****
Offline

Who said plumbing was
easy.
Posts: 6037


Total Thanks: 147
For This Post: 0


Gender: male

Trade: Plumber



Re: Baxi 105e Combi CH fault (only when boiler is cold
Reply #5 - Dec 7th, 2011, 5:49pm
 
Nope, Ill put the question to the baxi man and see what he says.
Back to top
 
Thank User For This Post View members image gallery  
IP Logged
 
Damoegan
Re: Baxi 105e Combi CH fault (only when boiler is cold
Reply #6 - Dec 7th, 2011, 7:02pm
 
thescruff wrote on Dec 7th, 2011, 5:49pm:
Nope, Ill put the question to the baxi man and see what he says.


Thanks matey, appreciate it  Smiley
Back to top
 
Thank User For This Post  
IP Logged
 
thescruff
Global Moderator
Trade Member
Author
*****
Offline

Who said plumbing was
easy.
Posts: 6037


Total Thanks: 147
For This Post: 0


Gender: male

Trade: Plumber



Re: Baxi 105e Combi CH fault (only when boiler is cold
Reply #7 - Dec 7th, 2011, 9:41pm
 
You need to get an RGI to check the high and low pressures, and the flame/ignition.

Back to top
 
Thank User For This Post View members image gallery  
IP Logged
 
Damoegan
Re: Baxi 105e Combi CH fault (only when boiler is cold
Reply #8 - Dec 7th, 2011, 10:22pm
 
thescruff wrote on Dec 7th, 2011, 9:41pm:
You need to get an RGI to check the high and low pressures, and the flame/ignition.



Thanks. The flame ignition looks to be working fine so I'll get someone to check out the high and low pressure.
Back to top
 
Thank User For This Post  
IP Logged
 
thescruff
Global Moderator
Trade Member
Author
*****
Offline

Who said plumbing was
easy.
Posts: 6037


Total Thanks: 147
For This Post: 0


Gender: male

Trade: Plumber



Re: Baxi 105e Combi CH fault (only when boiler is cold
Reply #9 - Dec 7th, 2011, 10:27pm
 
he should also check the gas valve and the gas governor on the meter.
Back to top
 
Thank User For This Post View members image gallery  
IP Logged
 