Central Heating hot water in head tank (Read 3065 times)
argus1946
GDPR opt-out









Central Heating hot water in head tank
Dec 19th, 2011, 8:40pm
 
20 yr old system thought I would look in the head tank and found hot water in there, stains down the inside of the tank sugest the hot water is coming in via the vent pipe. The system is indirect and has an oil fired boiler. Last time I looked in the tank about 7 yrs ago everything was ok.
Can anyone suggest what the fault is?

Argus
Back to top
 
 
IP Logged
 
thescruff
Global Moderator
Trade Member
Author
*****
Offline

Who said plumbing was
easy.
Posts: 6037


Total Thanks: 147
For This Post: 0


Gender: male

Trade: Plumber



Re: Central Heating hot water in head tank
Reply #1 - Dec 20th, 2011, 1:16am
 
Do you mean the smaller header tank for the heating.

If so you need to check what is happening, hold a glass of water under the vent pipe and turn the pump on and off a few times, does it suck the water out the jar or blow over.

Could be a blocked co0ld feed, but the info first.
Back to top
 
Thank User For This Post View members image gallery  
IP Logged
 
argus1946
Re: Central Heating hot water in head tank
Reply #2 - Dec 20th, 2011, 10:51am
 
Hi Scruff

Yes the small CH header tank

Hot water has flowed from the vent pipe into the tank its not continuous but had occured not long before I looked in and did not reoccur while I watched. It has been going for some time because there was a jelly like scum in the tank with a rusty colour and a rusty stain down the side of the tank where water from the vent has run down the side.

The system is working ok but is slow to get going all the radiators are ok.

Yesterday I installed a new circulating pump whist the system was drained down I was connecting a heated towel rail and decided to do the pump as well. I hoovered all the gunge out of the head tank put fresh fernox f1 in refilled and bled all the radiators. system started up ok but when I checked the head tank some reirculation had occured.

May not be able to do more until after the holiday - family pressure

Argus
Back to top
 
Thank User For This Post  
IP Logged
 
thescruff
Global Moderator
Trade Member
Author
*****
Offline

Who said plumbing was
easy.
Posts: 6037


Total Thanks: 147
For This Post: 0


Gender: male

Trade: Plumber



Re: Central Heating hot water in head tank
Reply #3 - Dec 20th, 2011, 11:21am
 
Can you raise the vent pipe so it is higher where it goes up and over the header tank.
Back to top
 
Thank User For This Post View members image gallery  
IP Logged
 
CWatters
Super Member
*****
Offline

"Daddy fick it" says James

Posts: 5150


Total Thanks: 58
For This Post: 0


Gender: male

Re: Central Heating hot water in head tank
Reply #4 - Dec 20th, 2011, 11:44pm
 
Double check where the feed and vent are in relation to the pump. I know you said it was working fine in the past but sometimes they work fine even with things in the wrong order...at least until something changes.