Just a small question del... the picture shows, in the "distance", what looks to me to be a noggin....between the rafters.....with the insulation going, up to it.... if that is the case, then surely, you have BLOCKED OFF any airflow within that section, and any others like it...
normally, if any of my clients are going to insulate, to give a "semi" warm roof, then i'd get the noggin's and either turn them through about 45 degs, or take eack one out, then add 2 set flat but staggered to still allow the air flow up between each rafter set!!!
|