Can RCD FCU be used
Oct 4th, 2012, 3:54pm
 
Hello

Newby here.  I am in need a bit of advise, there is an external socket installed on the conservatory wall in our house, but there is no RCD protection. I have attached a pic of the diagram that shows the wiring (its not great I know).

Basically the conservatory is wired from the upstairs socket ring via an unswitched FCU @ 13A in the 3rd bedroom, which feeds the light via a switched FCU fused @ 13A and 2 double plugs, one which the outside socket is connected to. Could I replace the unswitched FCU with an RCD FCU, to offer RCD protection to the whole of the conservatory.

Also if it can be done I have read about Passive or Active ones

Image 1

Any Help will be greatly appreciated
Back to top
 
 
IP Logged
 
Lectrician
Administrator
Trade Member
Author
*****
Offline

Ask The Trades
Posts: 8815


Total Thanks: 109
For This Post: 0


Braunton, North Devon, United Kingdom
Braunton, North Devon
United Kingdom

Gender: male

Trade: Electrician



Re: Can RCD FCU be used
Reply #1 - Oct 4th, 2012, 6:45pm
 
Yes, you can do that.

An active RCD will trip itself off during a power failure where as a passive one will not.

I would fit a passive one.
Back to top
 

Need to post a picture? Click HERE for info!
Thank User For This Post WWW View members image gallery  
IP Logged
 
Jonsey
Re: Can RCD FCU be used
Reply #2 - Oct 5th, 2012, 7:55am
 
Lectrician wrote on Oct 4th, 2012, 6:45pm:
Yes, you can do that.

An active RCD will trip itself off during a power failure where as a passive one will not.

I would fit a passive one.



Hi Lectrician

Thank you for your reply, as the conservatory houses no major appliances like fridge or freezer, could an active one be used as im not to fussed about poping upstairs to reset if it ever trips due to power failure.

Regards

Dave
Back to top
 
Thank User For This Post  
IP Logged
 
Lectrician
Administrator
Trade Member
Author
*****
Offline

Ask The Trades
Posts: 8815


Total Thanks: 109
For This Post: 0


Braunton, North Devon, United Kingdom
Braunton, North Devon
United Kingdom

Gender: male

Trade: Electrician



Re: Can RCD FCU be used
Reply #3 - Oct 5th, 2012, 8:44am
 
You can use either, it's just a convenience thing.
Back to top
 

Need to post a picture? Click HERE for info!
Thank User For This Post WWW View members image gallery  
IP Logged
 
The_Trician
Trade Member
*****
Offline


Posts: 7721


Total Thanks: 8
For This Post: 0


Gender: male

Trade: Electrician



Re: Can RCD FCU be used
Reply #4 - Oct 5th, 2012, 1:00pm
 
Just a quick observation -
You really ought to have another separate fused connection unit fitted with a 3A or 5A fuse to provide overcurrent protection for the conservatory light too.

TT
Back to top
 

Thats the trouble with a colostomy - you can never find the shoes to match the bag.......
Thank User For This Post  
IP Logged
 
Lectrician
Administrator
Trade Member
Author
*****
Offline

Ask The Trades
Posts: 8815


Total Thanks: 109
For This Post: 0


Braunton, North Devon, United Kingdom
Braunton, North Devon
United Kingdom

Gender: male

Trade: Electrician



Re: Can RCD FCU be used
Reply #5 - Oct 5th, 2012, 6:19pm
 
The_Trician wrote on Oct 5th, 2012, 1:00pm:
Just a quick observation -
You really ought to have another separate fused connection unit fitted with a 3A or 5A fuse to provide overcurrent protection for the conservatory light too.

TT

Its a switched fused spur for the lights, although it does show a 13amp fuse - should be a 3 amp.