Power surges when under high load (Read 4863 times)
AndrewMGlasgow
GDPR opt-out









Power surges when under high load
Mar 20th, 2013, 9:59pm
 
Hi all,

I have a problem - not sure how big or small it is.  For the last few months now, I have been suffering from intermittent flickering of my lights.  It is not just the lighting circuit which is affected, as I can see my lamps flickering and even the lamp inside my electric oven is affected too.

Sometimes I can run as many appliances I wish and there are no problems.  At other times, the flickering is quite concerning.  One night last week when I was trying to read it was actually offputting trying to read that I gave up!

Even with very little loads it does it.  When the flickering is taking place, it becomes more exaggerated the more appliances I run.  For example earlier tonight I had the oven on, the microwave, and the kettle, and the lights were flashing like a disco.

The property is an old tenement circa 120 years old.  This flat used to be part of the property upstairs, until it was subdivided in the mid 80s.

Consumer unit is a Memera 21.  Looks a fair age as if its been put in when the flat was done in the 80s.  Don't know how old the wiring is.

Initially I am thinking it is the consumer unit which is needing replaced.  The only change I can identify over the past few months is the property upstairs has became occupied and they could be running high demand appliances which is causing my surges.

Anyone have any advice on how I should proceed?  I want to get an electrician in but I don't want them telling me its a full rewiring job when its just the consumer unit which needs replaced, or even an external problem which the electricity network is responsible for.
Back to top
 
 
IP Logged
 
AndrewMGlasgow
GDPR opt-out









Re: Power surges when under high load
Reply #1 - Mar 20th, 2013, 10:51pm
 
...

This is the CU.

Don't like the look of lack of blanking plates, and the actual switches themselves don't appear to be secure/lined up properly.  Not sure if this is material.
Back to top
 
 
IP Logged
 
thescruff
Global Moderator
Trade Member
Author
*****
Offline

Who said plumbing was
easy.
Posts: 6037


Total Thanks: 147
For This Post: 0


Gender: male

Trade: Plumber



Re: Power surges when under high load
Reply #2 - Mar 20th, 2013, 11:58pm
 
Hi, Not a sparky so just a few questions for when the boss turns up in the morning.

Where is the property located, country, town etc.

Is it an overhead supply and if so are you on the end of the line.

Was the supply ok before they moved in upstairs.

Is it better at certain times of the day, when the upstairs is at work for example.
Back to top
 
Thank User For This Post View members image gallery  
IP Logged
 
Lectrician
Administrator
Trade Member
Author
*****
Offline

Ask The Trades
Posts: 8814


Total Thanks: 109
For This Post: 0


Braunton, North Devon, United Kingdom
Braunton, North Devon
United Kingdom

Gender: male

Trade: Electrician



Re: Power surges when under high load
Reply #3 - Mar 21st, 2013, 6:57am
 
This is usually down to a high resistance joint on the electricity supply to the flat.  More than likely outside before it enters the building.

Do other people in the block have similar issues?  Perhaps not everyone, but every third person (three phases).

Where is your electricity meter?  You are responsible for everything after this point, and it could be a loose connection between there and (or in) your consumer unit.

I would check for tightness and signs or overheating or a fishy smell inside your consumer unit, and inside the switched fuse after the meter (assuming there is one).  If all this looks OK, I would contact your DNO and report the problem to them (you may need to report via your supplier, as some DNO's do not allow direct contact).  They will then check their side, and if nothing found, will fit a logger to log the voltage and demand over a period of time (weeks even).  They will then check the data to see if the problem is theirs.
Back to top
 

Need to post a picture? Click HERE for info!
Thank User For This Post WWW View members image gallery  
IP Logged
 
AndrewMGlasgow
Re: Power surges when under high load
Reply #4 - Mar 21st, 2013, 10:31pm
 
Lectrician wrote on Mar 21st, 2013, 6:57am:
This is usually down to a high resistance joint on the electricity supply to the flat.  More than likely outside before it enters the building.

Do other people in the block have similar issues?  Perhaps not everyone, but every third person (three phases).

Where is your electricity meter?  You are responsible for everything after this point, and it could be a loose connection between there and (or in) your consumer unit.

I would check for tightness and signs or overheating or a fishy smell inside your consumer unit, and inside the switched fuse after the meter (assuming there is one).  If all this looks OK, I would contact your DNO and report the problem to them (you may need to report via your supplier, as some DNO's do not allow direct contact).  They will then check their side, and if nothing found, will fit a logger to log the voltage and demand over a period of time (weeks even).  They will then check the data to see if the problem is theirs.


Thats very useful, thanks for that.  Scottish Hydro are getting a call tmmw Smiley
Back to top
 
Thank User For This Post  
IP Logged
 
AndrewMGlasgow
Re: Power surges when under high load
Reply #5 - Mar 27th, 2013, 12:14am
 
Just to let everyone know what happened with this, after the surges getting very bad tonight I called ScottishPower Networks who took a look at the connection coming into the property from the common close, and found that the wire coming into the property had burnt out.  Was literally melting into the encasement of the switching gear.

The engineer replaced that wiring within half an hour, and now my lighting etc. is on solid regardless of how many applicances I run Smiley

One happy customer, no costs to me, and all is well.

Thanks for your guidance again.
Back to top
 
Thank User For This Post  
IP Logged
 
Natedog
Full Member
***
Offline

Ask The Trades
Posts: 343


Total Thanks: 9
For This Post: 0


Swindon, United Kingdom
Swindon
United Kingdom


Re: Power surges when under high load
Reply #6 - Mar 28th, 2013, 4:23pm
 
did they say why it had happened?
Back to top
 
Thank User For This Post WWW View members image gallery  
IP Logged
 
Lectrician
Administrator
Trade Member
Author
*****
Offline

Ask The Trades
Posts: 8814


Total Thanks: 109
For This Post: 0


Braunton, North Devon, United Kingdom
Braunton, North Devon
United Kingdom

Gender: male

Trade: Electrician



Re: Power surges when under high load
Reply #7 - Mar 28th, 2013, 8:07pm
 
Loose connection with a heavy load.  Bad combo.