baxi boiler (Read 2503 times)
ade911
GDPR opt-out









baxi boiler
Oct 28th, 2013, 3:08pm
 
on an baxi 105 e boiler I need to replace the pressure relief valve, as its leaking outside. Anyone know if I have to drain the system first? and tips will be great thanks
Ade
Back to top
 
 
IP Logged
 
Lectrician
Administrator
Trade Member
Author
*****
Offline

Ask The Trades
Posts: 8815


Total Thanks: 109
For This Post: 0


Braunton, North Devon, United Kingdom
Braunton, North Devon
United Kingdom

Gender: male

Trade: Electrician



Re: baxi boiler
Reply #1 - Oct 28th, 2013, 3:30pm
 
You would need to drain down at least the boiler - I am not familiar with the Baxi, but assume it would have an isolation valve on the flow and return pipework, and a drain-cock somewhere on the boiler.  You would then be able to change the PRV valve.

BUT...

Is this PRV valve 'leaking' because it has gone duff (some crap stuck to the valves seat, causing it to let by), or is it doing it's job?  Is the pressure in the system normal, or gone to high?  If it's gone too high, it could be due to a failed expansion vessel, or because mains water pressure it's finding it's way into the system via a dodgy filling loop, or a failed heat exchanger (combi DHW).

Scruff will help later...
Back to top
 

Need to post a picture? Click HERE for info!
Thank User For This Post WWW View members image gallery  
IP Logged
 
thescruff
Global Moderator
Trade Member
Author
*****
Offline

Who said plumbing was
easy.
Posts: 6037


Total Thanks: 147
For This Post: 0


Gender: male

Trade: Plumber



Re: baxi boiler
Reply #2 - Oct 28th, 2013, 4:14pm
 
Not a lot to say that hasn't been said.

Set the pressure at 1.4bar then post how high it goes when you turn the heating on.

As Lec posted, you likely have an expansion vessel problem.

No point changing the PRV until you know why it failed as the new one will do the same.
Back to top