Another (probably daft) question about sockets
Aug 1st, 2021, 1:15pm
 
I'm fitting some metalclad sockets inside a steel box that's going to house a cctv unit.  It's going to have 2x double sockets.  Someone suggested joining the 2 back boxes together with a 20mm conduit coupler and some threaded bushes, so they are one rigid unit.  

Usually you would put a rubber grommet on the knockout to stop the cable chafing.  If I join 2 boxes together, does it still need something to stop chafing, or is making sure there are no sharp or rough edges on the bush good enough?
Back to top
 
Thank User For This Post WWW View members image gallery  
IP Logged
 
Lectrician
Administrator
Trade Member
Author
*****
Offline

Ask The Trades
Posts: 8815


Total Thanks: 109
For This Post: 0


Braunton, North Devon, United Kingdom
Braunton, North Devon
United Kingdom

Gender: male

Trade: Electrician



Re: Another (probably daft) question about sockets
Reply #1 - Aug 8th, 2021, 9:01pm
 
No.  The bush is better than a grommet.  Conduit coupler and bushes to join boxes, a TRS gland to allow supply cable in.  It provides restraint, where a grommet won’t.
Back to top
 

Need to post a picture? Click HERE for info!
Thank User For This Post WWW View members image gallery  
IP Logged
 
Natedog
Full Member
***
Offline

Ask The Trades
Posts: 347


Total Thanks: 9
For This Post: 0


Swindon, United Kingdom
Swindon
United Kingdom


Re: Another (probably daft) question about sockets
Reply #2 - Aug 19th, 2021, 11:48pm
 
Thanks dude  Grin
Back to top
 
Thank User For This Post WWW View members image gallery  
IP Logged
 
Page Index Toggle Pages: 1
Send Topic Print