Hello - any help appreciated!!
I took out my oven and hob out the other day - both were connected via separte wires (10mm, double insulated) to a junction box and then on a circut run to the main fuse board in my flat, where they have a 30a old style fuse (ie with the wire) with a switch above the hob, which turns them both on/off.
I have not installed my new oven/hob yet as - My new hob says that it needs a 30a fuse (so this is fine - i have also checked the width of the existing wire, and this is fine also)
But my new oven says 20a max! My question is - would it be better to a) replace the fuse with a 20a and then hope that i dont blow it when i turn on the hob
or
b) have an electrician come round and run a separte wire to the fuse box + a new junction box to accommodate my new requirement of the 20a fuse for the oven
or
c) put them on the existing 30a fuse - but im assuming this may harm my oven as this says 20a max?
Is there some other way this could be done?
Thanks in advance anyone out there!
Jim