Hi, I'm new to this forum, but am at my wits end with my central heating system at the minute, and hoping some of you guys can help. I'll expain the situation briefly:
Gloworm 30cxi condensing combi boiler, installed in July 2007. I live in a 3 story mid terrace (basically, two floors plus a basement which includes the kitchen and cellar). The boiler is installed in the kitchen, but there is no central heating down there, so no pipework under concrete floors or embedded. All the CH pipework is under suspended floors leading on first and second floor, plus exposed in ceiling of cellar.
Problem started in April - noticed the boiler pressure had dropped to 0.6, but refilling loop was jammed. British Gas came out and changed it, refilled, etc - all fine.
CH turned off for summer, and no problems. 5 weeks ago, i turned the CH on and boiler started losing pressure again, topping up once every few days. I've had BG out 4 times now to check and they've done the following:
- replaced PRV - inflated expansion vessel (apparently it was flat)
However, it seems that since the expansion vessel was pumped up, the pressure loss is now daily, going from 1.5 bars to 0.6 bars and off within 15 - 20 hours. it seems to hold a lot better when the heating is on (i.e. raising by approx 0.5 bar) but drops within a few hours when off.
I isolated the CH flow and return valves on the boiler 3 times overnight - pressure held in boiler, and decreased by at least 0.3 bar as soon as the valves were opened. This points to a leak in the system. However...
there is no water marks or signs of a leak on any of the ceilings, which i would expect such a large leak to create over a month-long period. Also, a leak detection company came out and confirmed this without charging me, which i was really grateful for. I've even had all the floorboards up in the one room which i thought could be the offender, but nothing.
I've checked all visible pipework for a leak, including radiator valves, bled radiators, even left whilte paper under then to see if this would identify any leaks - and nothing!
I'm at my wits end here - noone seems to know what the problem is - however, this is more than an inconvenience, as I'm aware that refilling the boiler every day is introducing oxygen into the system which is not good in the long term.
Any advice would be gratefully received. If it's not the boiler or the pipework, i really don't understand what else it could be!!
|