Welcome, Guest. Please Login or Register
Welcome To Ask The Trades!
Dec 30th, 2025, 1:37pm
Quote: Never look down on anybody unless you're helping him up - Jesse Jackson


Page Index Toggle Pages: 1
Send Topic Print
Equipotential Bonding (Read 8202 times)
GarethH
GDPR opt-out









Equipotential Bonding
Oct 2nd, 2011, 8:33pm
 
Hi All,

I need to get a spark in to replace my old wylex fuse box with a new 17th edition CU. I understand this would require main equipotential bonding to the gas and water services (which are both in copper).

My 1970s house doesn't have main equipotential bonding but installing it is non-notifiable so I want to do it myself to save some cash. Sod's law has dictated that the gas and water meters are nowhere near the electricity meter and CU so running the 10mm2 earth cable will take time.

I tried to find the MET so I looked in the meter cupboard. There's an earth terminal in the box that houses the 100A fuse. Connected to that is a piece of thin (probably 2.5 mm2) earth cable going to the consumer unit. There's no additional earth wiring in there. 3 cables (two meter tails and the earth go through the wall to the fuse box).

The earth bar in the fuse box just connects that earth wire and all of the earths from the other circuits together; there's no earth going off to an earth rod.

My questions are:

1. When the new CU is installed, will it contain the MET (i.e. do I run the 2x 10mm2 earth bonding cables to the location of the new CU

2. Is the current 2.5mm earth cable typical of a 1970s house (I presume this needs upgrading when the CU is replaced)?

3. Is the system definitely TN-S or TN-C-S (not TT) - there isn't an earth rod / MET that I might have missed.

4. Is it acceptable to run the 10mm2 earth bonding cable on the outside of the property?

Cheers

Gareth
Back to top
 
 
IP Logged
 
Lectrician
Administrator
Trade Member
Author
*****
Offline

Ask The Trades
Posts: 8815


Total Thanks: 109
For This Post: 0


Braunton, North Devon, United Kingdom
Braunton, North Devon
United Kingdom

Gender: male

Trade: Electrician



Re: Equipotential Bonding
Reply #1 - Oct 2nd, 2011, 8:49pm
 
The 10mm² bonding conductors can be terminated into the consumer unit - the earth bar of a consumer unit can be used as your MET.

You would need to replace the 2.5mm earth to the service head.

Certainly sounds like a TN-C-S or TN-S - a photo would confirm.

The bonding cable may be run externally, although not cable tied to a gas pipe etc.  Extra mechanical protection is at the installers discretion (likely hood of damage etc)

If the gas and water are close by and it is easier, you can use a single run of 10mm².  You would pass it through one clamp and onto the next WITHOUT cutting the cable.
Back to top
 

Need to post a picture? Click HERE for info!
Thank User For This Post WWW View members image gallery  
IP Logged
 
GarethH
Re: Equipotential Bonding
Reply #2 - Oct 3rd, 2011, 6:41pm
 
Thanks for your reply. Here's a photo of the service head and meter.

Image 1

I've just had a thought - my water main is a plastic pipe which is converted to metal just before the meter. As the metal does not extend outside the equipotental zone of the house, is equipotential bonding required for that service?

What I've read suggests that only extraneous conductive parts of the location require bonding. I interpret this as parts of the location which are both extraneous and conductive. The water main is extraneous but isn't conductive.
Back to top
 
Thank User For This Post  
IP Logged
 
Lectrician
Administrator
Trade Member
Author
*****
Offline

Ask The Trades
Posts: 8815


Total Thanks: 109
For This Post: 0


Braunton, North Devon, United Kingdom
Braunton, North Devon
United Kingdom

Gender: male

Trade: Electrician



Re: Equipotential Bonding
Reply #3 - Oct 5th, 2011, 5:27pm
 
You have either a TN-C-S or TN-S system.  Not a TT.  Difficult to tell for sure if it is TN-C-S or TN-S.

If the supply pipe is plastic, the NICEIC still strongly recommend that main protective equipotential bonding is installed if the pipework within the installation is copper.
Back to top
 

Need to post a picture? Click HERE for info!
Thank User For This Post WWW View members image gallery  
IP Logged
 
GarethH
Re: Equipotential Bonding
Reply #4 - Oct 8th, 2011, 5:34pm
 
I'll bond it then!

Thanks for the help
Back to top
 
Thank User For This Post  
IP Logged
 
LSpark
Global Moderator
Trade Member
Author
*****
Offline


Posts: 8069


Total Thanks: 3
For This Post: 0


London, UK, United Kingdom
London, UK
United Kingdom

Gender: male

Trade: Electrician



Re: Equipotential Bonding
Reply #5 - Oct 12th, 2011, 8:24pm
 
Lectrician wrote on Oct 5th, 2011, 5:27pm:
If the supply pipe is plastic, the NICEIC still strongly recommend that main protective equipotential bonding is installed if the pipework within the installation is copper.

I'd forgotten about how the NIC like to make up their own rules. We all know earthing can cause dangers as well as prevent them!
Back to top
 
Thank User For This Post View members image gallery  
IP Logged
 
Page Index Toggle Pages: 1
Send Topic Print